'CR1000 Series Datalogger ' program name: Library2_2009-05-29.CR1 ' program modified: Library2_2009-5-28.CR1 ' modified by: AMcHugh ' fixed location of TMaxHWT_F and RadTankHWT_F pulled out of SolDomHot.dat tables and moved to DailySolHkdrnc.dat tables ' program name: Library2_2009-05-28.CR1 ' program modified: Library2_2008-10-29.CR1 ' modified by: AMcHugh ' added DomTankHWT_F, TMaxHWT_F, and RadTankHWT_F values to SolDomHot.dat tables. ' program name: Library2_2008-10-29.CR1 ' program modified: Library2_2008-10-23test.CR1 ' - removed x100 on PV1,2,3,4 Lo and BldgLo per request of Kristen and JonM ' program modified: Library2_2008-9-15.CR1 ' - added 15min, hourly, and daily usage values. ' - also changed a bunch of the *100 values to match JonMs table. ' program modified: Library2_2008-7-23.CR1 ' - Fixed several modbus values that were off by /100 because JonMartin did not x by 100 because they got too big ' for the Siemens firmware to deal with. ' - I edited the logger code to not divide by 100 the ones that don't need it. ' - The values that JonMartin did not x100 have the units _G, _ppm, or end with SS or Vlv. ' added variable names 'Declare Public Variables 'Example: Public LoggerTemp_C, BattVolts_V ' The ModBus variable must be configured As Long because it comes as an integer. Public Result Public ModbusVarFloat(100), ModbusVar2Float(46) Public QuarterHrUsage_kw, HourlyUsage_kw, DailyUsage_kw Dim LastQHBldgLo, LastHourlyBldgLo, LastDailyBldgLo 'these are from the previous interval Dim ModbusVariable(100) As Long, ModbusVariable2(100) As Long Dim i Alias ModbusVarFloat(1) = Blr1Fuel_G 'Radiant Heating Alias ModbusVarFloat(2) = Blr2Fuel_G 'Basement/Lab Heatting Alias ModbusVarFloat(3) = Blr3Fuel_G 'Basement/Lab Heatting Alias ModbusVarFloat(4) = OAT_F 'Environmental x100 Alias ModbusVarFloat(5) = OAH_Pct 'Environmental x100 Alias ModbusVarFloat(6) = BlrSupTemp_F 'Radiant Heating x100 Alias ModbusVarFloat(7) = BlrRetTemp_F 'Radiant Heating x100 Alias ModbusVarFloat(8) = Blr1Stack_F 'Radiant Heating x100 Alias ModbusVarFloat(9) = Blr2Stack_F 'Basement/Lab Heatting x100 Alias ModbusVarFloat(10) = Blr3Stack_F 'Basement/Lab Heatting x100 Alias ModbusVarFloat(11) = RadPumpSS 'Solar Hydronic Alias ModbusVarFloat(12) = TMaxPumpSS 'Solar Hydronic Alias ModbusVarFloat(13) = PV1VDC_VDC 'PhotoVoltaic x100 Alias ModbusVarFloat(14) = PV2VDC_VDC 'PhotoVoltaic x100 Alias ModbusVarFloat(15) = PV3VDC_VDC 'PhotoVoltaic x100 Alias ModbusVarFloat(16) = PV4VDC_VDC 'PhotoVoltaic x100 Alias ModbusVarFloat(17) = PV1Amps_A 'PhotoVoltaic x100 Alias ModbusVarFloat(18) = PV2Amps_A 'PhotoVoltaic x100 Alias ModbusVarFloat(19) = PV3Amps_A 'PhotoVoltaic x100 Alias ModbusVarFloat(20) = PV4Amps_A 'PhotoVoltaic x100 Alias ModbusVarFloat(21) = HRV1CO2_ppm 'Environmental Alias ModbusVarFloat(22) = HRV1RMT_F 'Environmental x100 Alias ModbusVarFloat(23) = HRV1RMH_Pct 'Environmental x100 Alias ModbusVarFloat(24) = DomTank1Lvl_ft 'Domestic Water x100 Alias ModbusVarFloat(25) = DomTank2Lvl_ft 'Domestic Water x100 Alias ModbusVarFloat(26) = HRV21CO2_ppm 'Environmental Alias ModbusVarFloat(27) = HRV21RMT_F 'Environmental x100 Alias ModbusVarFloat(28) = HRV21RMH_pct 'Environmental x100 Alias ModbusVarFloat(29) = HRV22CO2_ppm 'Environmental Alias ModbusVarFloat(30) = HRV22RMT_F 'Environmental x100 Alias ModbusVarFloat(31) = HRV22RMH_pct 'Environmental x100 Alias ModbusVarFloat(32) = HRV2SAT_F 'Environmental x100 Alias ModbusVarFloat(33) = HRV3SAT_F 'Environmental x100 Alias ModbusVarFloat(34) = HRV3CO2_ppm 'Environmental Alias ModbusVarFloat(35) = DomTankHWT_F 'Solar Domestic Hot Water x100 Alias ModbusVarFloat(36) = RadTankHWT_F 'Solar Hydronic x100 Alias ModbusVarFloat(37) = TMaxHST_F 'Solar Hydronic x100 Alias ModbusVarFloat(38) = TMaxHWT_F 'Solar Hydronic x100 Alias ModbusVarFloat(39) = RadMixVlv_pct 'Solar Hydronic x100 Alias ModbusVarFloat(40) = TMaxHDVlv 'Solar Hydronic x100 Alias ModbusVarFloat(41) = SolarBlrVlv 'Solar Hydronic Alias ModbusVarFloat(42) = HelioHDVlv 'Solar Domestic Hot Water Alias ModbusVarFloat(43) = HRV42RMT_F 'Environmental x100 Alias ModbusVarFloat(44) = HRV41CO2_ppm 'Environmental Alias ModbusVarFloat(45) = HRV41RMT_F 'Environmental x100 Alias ModbusVarFloat(46) = HRV41RMH_pct 'Environmental x100 Alias ModbusVarFloat(47) = HRV42CO2_ppm 'Environmental x100 Alias ModbusVarFloat(48) = HRV42RMH_pct 'Environmental x100 Alias ModbusVarFloat(49) = HRV4SAT_F 'Environmental x100 Alias ModbusVarFloat(50) = OACO2_ppm 'Environmental Alias ModbusVarFloat(51) = HRV5CO2_ppm 'Environmental Alias ModbusVarFloat(52) = HRV5RMT_F 'Environmental x100 Alias ModbusVarFloat(53) = HRV5RMH_pct 'Environmental x100 Alias ModbusVarFloat(54) = HRV5SAT_F 'Environmental x100 Alias ModbusVarFloat(55) = HRV5RAT_F 'Environmental x100 Alias ModbusVarFloat(56) = HRV5MAD_pct 'Environmental x100 Alias ModbusVarFloat(57) = Stair05T_F' RM05RMT_F 'Environmental 'Stair 05 Temp x100 Alias ModbusVarFloat(58) = Elev07T_F' RM07RMT_F 'Environmental 'Elev 07 Temp x100 Alias ModbusVarFloat(59) = Stair111T_F ' RM111RMT_F 'Environmental ' Stair 111 Temp x100 Alias ModbusVarFloat(60) = Elev112T_F ' RM112RMT_F 'Environmental ' Elev 112 Temp x100 Alias ModbusVarFloat(61) = SLOffice116T_F ' RM116RMT_F 'Environmental 'SL Office 116 Temp x100 Alias ModbusVarFloat(62) = BackDoor117T_F ' RM117RMT_F 'Environmental ' Back Door 117 Temp x100 Alias ModbusVarFloat(63) = Elev210T_F ' RM210RMT_F 'Environmental ' Elev 210 Temp x100 Alias ModbusVarFloat(64) = FrontMes211T_F ' RM211RMT_F 'Environmental ' Front Mes 211 Temp x100 Alias ModbusVarFloat(65) = Tech213T_F ' RM213RMT_F 'Environmental 'Tech 213 Temp x100 Alias ModbusVarFloat(66) = RearMes215T_F ' RM215RMT_F 'Environmental ' Rear Mes 215 Temp x100 Alias ModbusVarFloat(67) = MensRR217F_F ' RM217RMT_F 'Environmental 'Mens RR 217 Temp x100 Alias ModbusVarFloat(68) = BLR1BTU_BTU_H 'Radiant Heating x100 Alias ModbusVarFloat(69) = BLR1Vol_GPM 'Radiant Heating x100 Alias ModbusVarFloat(70) = BLR1ST_F 'Radiant Heating x100 Alias ModbusVarFloat(71) = BLR1RT_F 'Radiant Heating x100 Alias ModbusVarFloat(72) = BLR1DT_F 'Radiant Heating x100 Alias ModbusVarFloat(73) = BLR1TBTU_BTU 'Radiant Heating Alias ModbusVarFloat(74) = BLR2BTU_BTU_H 'Basement/Lab Heating x100 Alias ModbusVarFloat(75) = BLR2Vol_GPM 'Basement/Lab Heating 'JonM had this units as G 'Kristen says these should be GPH x100 Alias ModbusVarFloat(76) = BLR2ST_F 'Basement/Lab Heating x100 Alias ModbusVarFloat(77) = BLR2RT_F 'Basement/Lab Heating x100 Alias ModbusVarFloat(78) = BLR2DT_F'Basement/Lab Heating x100 Alias ModbusVarFloat(79) = BLR2TBTU_BTU'Basement/Lab Heating Alias ModbusVarFloat(80) = BLR3BTU_BTU_H'Basement/Lab Heating x100 Alias ModbusVarFloat(81) = BLR3Vol_GPM 'Basement/Lab Heating 'JonM had this units as G 'Kristen says these should be GPH Alias ModbusVarFloat(82) = BLR3ST_F 'Basement/Lab Heating x100 Alias ModbusVarFloat(83) = BLR3RT_F 'Basement/Lab Heating x100 Alias ModbusVarFloat(84) = BLR3DT_F 'Basement/Lab Heating x100 Alias ModbusVarFloat(85) = BLR3TBTU_BTU 'Basement/Lab Heating Alias ModbusVarFloat(86) = RadTankBTU_BTU_H 'Solar Hydronic x100 Alias ModbusVarFloat(87) = RadTankVol_GPH 'Solar Hydronic x100 Alias ModbusVarFloat(88) = RadTankST_F 'Solar Hydronic x100 Alias ModbusVarFloat(89) = RadTankRT_F 'Solar Hydronic x100 Alias ModbusVarFloat(90) = RadTankDT_F 'Solar Hydronic x100 Alias ModbusVarFloat(91) = RadTankTBTU_BTU 'Solar Hydronic Alias ModbusVarFloat(92) = TMaxHDBTU_BTU_H 'Solar Hydronic x100 Alias ModbusVarFloat(93) = TMaxHDVol_GPH 'Solar Hydronic x100 Alias ModbusVarFloat(94) = TMaxHDST_F 'Solar Hydronic x100 Alias ModbusVarFloat(95) = TMaxHDRT_F 'Solar Hydronic x100 Alias ModbusVarFloat(96) = TMaxHDDT_F 'Solar Hydronic x100 Alias ModbusVarFloat(97) = TMaxHDTBTU_BTU 'Solar Hydronic Alias ModbusVarFloat(98) = TMaxBTU_BTU_H 'Solar Hydronic x100 Alias ModbusVarFloat(99) = TMaxVol_GPH 'Solar Hydronic x100 Alias ModbusVarFloat(100) = TMaxST_F 'Solar Hydronic x100 Alias ModbusVar2Float(1) = TMaxRT_F 'Solar Hydronic x100 Alias ModbusVar2Float(2) = TMaxDT_F 'Solar Hydronic x100 Alias ModbusVar2Float(3) = TMaxTBTU_BTU 'Solar Hydronic Alias ModbusVar2Float(4) = DomBTU_BTU_H 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(5) = DomVol_GPH 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(6) = DomST_F 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(7) = DomRT_F 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(8) = DomDT_F 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(9) = DomTBTU_BTU 'Solar Domestic Hot Water Alias ModbusVar2Float(10) = HelioBTU_BTU_H 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(11) = HelioVol_GPH 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(12) = HelioST_F 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(13) = HelioRT_F 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(14) = HelioDT_F 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(15) = HelioTBTU_BTU 'Solar Domestic Hot Water Alias ModbusVar2Float(16) = HelioHDBTU_BTU_H 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(17) = HelioHDVol_GPH 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(18) = HelioHDST_F 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(19) = HelioHDRT_F 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(20) = HelioHDDT_F 'Solar Domestic Hot Water x100 Alias ModbusVar2Float(21) = HelioHDTBTU_BTU 'Solar Domestic Hot Water Alias ModbusVar2Float(22) = BldgLo_kw 'Energy Consumption Alias ModbusVar2Float(23) = BldgHi_kw 'Energy Consumption /100 (yes divide) Alias ModbusVar2Float(24) = BldgDemand_kw 'Energy Consumption x100 Alias ModbusVar2Float(25) = BldgPwrFac 'Energy Consumption x100 Alias ModbusVar2Float(26) = BldgCurrent_A 'Energy Consumption x100 Alias ModbusVar2Float(27) = PV1Lo_kw 'PhotoVoltaic Alias ModbusVar2Float(28) = PV1Hi_kw 'PhotoVoltaic Alias ModbusVar2Float(29) = PV1Demand_kw 'PhotoVoltaic x100 Alias ModbusVar2Float(30) = PV1PwrFac 'PhotoVoltaic x100 Alias ModbusVar2Float(31) = PV1Current_A 'PhotoVoltaic x100 Alias ModbusVar2Float(32) = PV2Lo_kw 'PhotoVoltaic Alias ModbusVar2Float(33) = PV2Hi_kw 'PhotoVoltaic Alias ModbusVar2Float(34) = PV2Demand_kw 'PhotoVoltaic x100 Alias ModbusVar2Float(35) = PV2PwrFac 'PhotoVoltaic x100 Alias ModbusVar2Float(36) = PV2Current_A 'PhotoVoltaic x100 Alias ModbusVar2Float(37) = PV3Lo_kw 'PhotoVoltaic Alias ModbusVar2Float(38) = PV3Hi_kw 'PhotoVoltaic Alias ModbusVar2Float(39) = PV3Demand_kw 'PhotoVoltaic x100 Alias ModbusVar2Float(40) = PV3PwrFac 'PhotoVoltaic x100 Alias ModbusVar2Float(41) = PV3Current_A 'PhotoVoltaic x100 Alias ModbusVar2Float(42) = PV4Lo_kw 'PhotoVoltaic Alias ModbusVar2Float(43) = PV4Hi_kw 'PhotoVoltaic Alias ModbusVar2Float(44) = PV4Demand_kw 'PhotoVoltaic x100 Alias ModbusVar2Float(45) = PV4PwrFac 'PhotoVoltaic x100 Alias ModbusVar2Float(46) = PV4Current_A 'PhotoVoltaic x100 'Declare Other Variables 'Example: 'Dim Counter 'Declare Constants 'Example: 'CONST PI = 3.141592654 'Define Data Tables DataTable (HourlyDiag,1,-1) DataInterval (0,60,Min,10) Sample (1,LoggerTemp_C,FP2) Average (1,LoggerTemp_C,FP2,False) Sample (1,BattVolts_V,FP2) Average (1,BattVolts_V,FP2,False) Maximum (1,BattVolts_V,FP2,False,False) Minimum (1,BattVolts_V,FP2,0,False) EndTable '15 minute tables DataTable (FifteenMinRadHeat,True,-1) DataInterval (0,15,Min,10) Sample (1,Blr1Fuel_G,FP2) Sample (1,BlrSupTemp_F,FP2) Sample (1,BlrRetTemp_F,FP2) Sample (1,Blr1Stack_F,FP2) Sample (1,BLR1BTU_BTU_H,FP2) Sample (1,BLR1Vol_GPM,FP2) Sample (1,BLR1ST_F,FP2) Sample (1,BLR1RT_F,FP2) Sample (1,BLR1DT_F,FP2) Sample (1,BLR1TBTU_BTU,FP2) Average (1,Blr1Fuel_G,FP2,False) Average (1,BlrSupTemp_F,FP2,False) Average (1,BlrRetTemp_F,FP2,False) Average (1,Blr1Stack_F,FP2,False) Average (1,BLR1BTU_BTU_H,FP2,False) Average (1,BLR1Vol_GPM,FP2,False) Average (1,BLR1ST_F,FP2,False) Average (1,BLR1RT_F,FP2,False) Average (1,BLR1DT_F,FP2,False) Average (1,BLR1TBTU_BTU,FP2,False) Maximum (1,Blr1Fuel_G,FP2,False,False) Maximum (1,BlrSupTemp_F,FP2,False,False) Maximum (1,BlrRetTemp_F,FP2,False,False) Maximum (1,Blr1Stack_F,FP2,False,False) Maximum (1,BLR1BTU_BTU_H,FP2,False,False) Maximum (1,BLR1Vol_GPM,FP2,False,False) Maximum (1,BLR1ST_F,FP2,False,False) Maximum (1,BLR1RT_F,FP2,False,False) Maximum (1,BLR1DT_F,FP2,False,False) Maximum (1,BLR1TBTU_BTU,FP2,False,False) Minimum (1,Blr1Fuel_G,FP2,False,False) Minimum (1,BlrSupTemp_F,FP2,False,False) Minimum (1,BlrRetTemp_F,FP2,False,False) Minimum (1,Blr1Stack_F,FP2,False,False) Minimum (1,BLR1BTU_BTU_H,FP2,False,False) Minimum (1,BLR1Vol_GPM,FP2,False,False) Minimum (1,BLR1ST_F,FP2,False,False) Minimum (1,BLR1RT_F,FP2,False,False) Minimum (1,BLR1DT_F,FP2,False,False) Minimum (1,BLR1TBTU_BTU,FP2,False,False) EndTable DataTable (FifteenMinBsmntLabHt,1,-1) DataInterval (0,15,Min,10) Sample (1,Blr2Fuel_G,FP2) Sample (1,Blr3Fuel_G,FP2) Sample (1,Blr2Stack_F,FP2) Sample (1,Blr3Stack_F,FP2) Sample (1,BLR2BTU_BTU_H,FP2) Sample (1,BLR2Vol_GPM,FP2) Sample (1,BLR2ST_F,FP2) Sample (1,BLR2RT_F,FP2) Sample (1,BLR2DT_F,FP2) Sample (1,BLR2TBTU_BTU,FP2) Sample (1,BLR3BTU_BTU_H,FP2) Sample (1,BLR3Vol_GPM,FP2) Sample (1,BLR3ST_F,FP2) Sample (1,BLR3RT_F,FP2) Sample (1,BLR3DT_F,FP2) Sample (1,BLR3TBTU_BTU,FP2) Average (1,Blr2Fuel_G,FP2,False) Average (1,Blr3Fuel_G,FP2,False) Average (1,Blr2Stack_F,FP2,False) Average (1,Blr3Stack_F,FP2,False) Average (1,BLR2BTU_BTU_H,FP2,False) Average (1,BLR2Vol_GPM,FP2,False) Average (1,BLR2ST_F,FP2,False) Average (1,BLR2RT_F,FP2,False) Average (1,BLR2DT_F,FP2,False) Average (1,BLR2TBTU_BTU,FP2,False) Average (1,BLR3BTU_BTU_H,FP2,False) Average (1,BLR3Vol_GPM,FP2,False) Average (1,BLR3ST_F,FP2,False) Average (1,BLR3RT_F,FP2,False) Average (1,BLR3DT_F,FP2,False) Average (1,BLR3TBTU_BTU,FP2,False) Maximum (1,Blr2Fuel_G,FP2,False,False) Maximum (1,Blr3Fuel_G,FP2,False,False) Maximum (1,Blr2Stack_F,FP2,False,False) Maximum (1,Blr3Stack_F,FP2,False,False) Maximum (1,BLR2BTU_BTU_H,FP2,False,False) Maximum (1,BLR2Vol_GPM,FP2,False,False) Maximum (1,BLR2ST_F,FP2,False,False) Maximum (1,BLR2RT_F,FP2,False,False) Maximum (1,BLR2DT_F,FP2,False,False) Maximum (1,BLR2TBTU_BTU,FP2,False,False) Maximum (1,BLR3BTU_BTU_H,FP2,False,False) Maximum (1,BLR3Vol_GPM,FP2,False,False) Maximum (1,BLR3ST_F,FP2,False,False) Maximum (1,BLR3RT_F,FP2,False,False) Maximum (1,BLR3DT_F,FP2,False,False) Maximum (1,BLR3TBTU_BTU,FP2,False,False) Minimum (1,Blr2Fuel_G,FP2,False,False) Minimum (1,Blr3Fuel_G,FP2,False,False) Minimum (1,Blr2Stack_F,FP2,False,False) Minimum (1,Blr3Stack_F,FP2,False,False) Minimum (1,BLR2BTU_BTU_H,FP2,False,False) Minimum (1,BLR2Vol_GPM,FP2,False,False) Minimum (1,BLR2ST_F,FP2,False,False) Minimum (1,BLR2RT_F,FP2,False,False) Minimum (1,BLR2DT_F,FP2,False,False) Minimum (1,BLR2TBTU_BTU,FP2,False,False) Minimum (1,BLR3BTU_BTU_H,FP2,False,False) Minimum (1,BLR3Vol_GPM,FP2,False,False) Minimum (1,BLR3ST_F,FP2,False,False) Minimum (1,BLR3RT_F,FP2,False,False) Minimum (1,BLR3DT_F,FP2,False,False) Minimum (1,BLR3TBTU_BTU,FP2,False,False) EndTable DataTable (FifteenMinEnv,1,-1) DataInterval (0,15,Min,10) Sample (1,OAT_F,FP2) Sample (1,OAH_Pct,FP2) Sample (1,HRV1CO2_ppm,FP2) Sample (1,HRV1RMT_F,FP2) Sample (1,HRV1RMH_Pct,FP2) Sample (1,HRV21CO2_ppm,FP2) Sample (1,HRV21RMT_F,FP2) Sample (1,HRV21RMH_pct,FP2) Sample (1,HRV22CO2_ppm,FP2) Sample (1,HRV22RMT_F,FP2) Sample (1,HRV22RMH_pct,FP2) Sample (1,HRV2SAT_F,FP2) Sample (1,HRV3SAT_F,FP2) Sample (1,HRV3CO2_ppm,FP2) Sample (1,HRV42RMT_F,FP2) Sample (1,HRV41RMH_pct,FP2) Sample (1,HRV4SAT_F,FP2) Sample (1,OACO2_ppm,FP2) Sample (1,HRV5CO2_ppm,FP2) Sample (1,HRV5RMT_F,FP2) Sample (1,HRV5RMH_pct,FP2) Sample (1,HRV5SAT_F,FP2) Sample (1,HRV5RAT_F,FP2) Sample (1,HRV5MAD_pct,FP2) Sample (1,Stair05T_F,FP2) Sample (1,Elev07T_F,FP2) Sample (1,Stair111T_F,FP2) Sample (1,Elev112T_F,FP2) Sample (1,SLOffice116T_F,FP2) Sample (1,BackDoor117T_F,FP2) Sample (1,Elev210T_F,FP2) Sample (1,FrontMes211T_F,FP2) Sample (1,Tech213T_F,FP2) Sample (1,RearMes215T_F,FP2) Sample (1,MensRR217F_F,FP2) Average (1,OAT_F,FP2,False) Average (1,OAH_Pct,FP2,False) Average (1,HRV1CO2_ppm,FP2,False) Average (1,HRV1RMT_F,FP2,False) Average (1,HRV1RMH_Pct,FP2,False) Average (1,HRV21CO2_ppm,FP2,False) Average (1,HRV21RMT_F,FP2,False) Average (1,HRV21RMH_pct,FP2,False) Average (1,HRV22CO2_ppm,FP2,False) Average (1,HRV22RMT_F,FP2,False) Average (1,HRV22RMH_pct,FP2,False) Average (1,HRV2SAT_F,FP2,False) Average (1,HRV3SAT_F,FP2,False) Average (1,HRV3CO2_ppm,FP2,False) Average (1,HRV42RMT_F,FP2,False) Average (1,HRV41RMH_pct,FP2,False) Average (1,HRV4SAT_F,FP2,False) Average (1,OACO2_ppm,FP2,False) Average (1,HRV5CO2_ppm,FP2,False) Average (1,HRV5RMT_F,FP2,False) Average (1,HRV5RMH_pct,FP2,False) Average (1,HRV5SAT_F,FP2,False) Average (1,HRV5RAT_F,FP2,False) Average (1,HRV5MAD_pct,FP2,False) Average (1,Stair05T_F,FP2,False) Average (1,Elev07T_F,FP2,False) Average (1,Stair111T_F,FP2,False) Average (1,Elev112T_F,FP2,False) Average (1,SLOffice116T_F,FP2,False) Average (1,BackDoor117T_F,FP2,False) Average (1,Elev210T_F,FP2,False) Average (1,FrontMes211T_F,FP2,False) Average (1,Tech213T_F,FP2,False) Average (1,RearMes215T_F,FP2,False) Average (1,MensRR217F_F,FP2,False) Maximum (1,OAT_F,FP2,False,False) Maximum (1,OAH_Pct,FP2,False,False) Maximum (1,HRV1CO2_ppm,FP2,False,False) Maximum (1,HRV1RMT_F,FP2,False,False) Maximum (1,HRV1RMH_Pct,FP2,False,False) Maximum (1,HRV21CO2_ppm,FP2,False,False) Maximum (1,HRV21RMT_F,FP2,False,False) Maximum (1,HRV21RMH_pct,FP2,False,False) Maximum (1,HRV22CO2_ppm,FP2,False,False) Maximum (1,HRV22RMT_F,FP2,False,False) Maximum (1,HRV22RMH_pct,FP2,False,False) Maximum (1,HRV2SAT_F,FP2,False,False) Maximum (1,HRV3SAT_F,FP2,False,False) Maximum (1,HRV3CO2_ppm,FP2,False,False) Maximum (1,HRV42RMT_F,FP2,False,False) Maximum (1,HRV41RMH_pct,FP2,False,False) Maximum (1,HRV4SAT_F,FP2,False,False) Maximum (1,OACO2_ppm,FP2,False,False) Maximum (1,HRV5CO2_ppm,FP2,False,False) Maximum (1,HRV5RMT_F,FP2,False,False) Maximum (1,HRV5RMH_pct,FP2,False,False) Maximum (1,HRV5SAT_F,FP2,False,False) Maximum (1,HRV5RAT_F,FP2,False,False) Maximum (1,HRV5MAD_pct,FP2,False,False) Maximum (1,Stair05T_F,FP2,False,False) Maximum (1,Elev07T_F,FP2,False,False) Maximum (1,Stair111T_F,FP2,False,False) Maximum (1,Elev112T_F,FP2,False,False) Maximum (1,SLOffice116T_F,FP2,False,False) Maximum (1,BackDoor117T_F,FP2,False,False) Maximum (1,Elev210T_F,FP2,False,False) Maximum (1,FrontMes211T_F,FP2,False,False) Maximum (1,Tech213T_F,FP2,False,False) Maximum (1,RearMes215T_F,FP2,False,False) Maximum (1,MensRR217F_F,FP2,False,False) Minimum (1,OAT_F,FP2,False,False) Minimum (1,OAH_Pct,FP2,False,False) Minimum (1,HRV1CO2_ppm,FP2,False,False) Minimum (1,HRV1RMT_F,FP2,False,False) Minimum (1,HRV1RMH_Pct,FP2,False,False) Minimum (1,HRV21CO2_ppm,FP2,False,False) Minimum (1,HRV21RMT_F,FP2,False,False) Minimum (1,HRV21RMH_pct,FP2,False,False) Minimum (1,HRV22CO2_ppm,FP2,False,False) Minimum (1,HRV22RMT_F,FP2,False,False) Minimum (1,HRV22RMH_pct,FP2,False,False) Minimum (1,HRV2SAT_F,FP2,False,False) Minimum (1,HRV3SAT_F,FP2,False,False) Minimum (1,HRV3CO2_ppm,FP2,False,False) Minimum (1,HRV42RMT_F,FP2,False,False) Minimum (1,HRV41RMH_pct,FP2,False,False) Minimum (1,HRV4SAT_F,FP2,False,False) Minimum (1,OACO2_ppm,FP2,False,False) Minimum (1,HRV5CO2_ppm,FP2,False,False) Minimum (1,HRV5RMT_F,FP2,False,False) Minimum (1,HRV5RMH_pct,FP2,False,False) Minimum (1,HRV5SAT_F,FP2,False,False) Minimum (1,HRV5RAT_F,FP2,False,False) Minimum (1,HRV5MAD_pct,FP2,False,False) Minimum (1,Stair05T_F,FP2,False,False) Minimum (1,Elev07T_F,FP2,False,False) Minimum (1,Stair111T_F,FP2,False,False) Minimum (1,Elev112T_F,FP2,False,False) Minimum (1,SLOffice116T_F,FP2,False,False) Minimum (1,BackDoor117T_F,FP2,False,False) Minimum (1,Elev210T_F,FP2,False,False) Minimum (1,FrontMes211T_F,FP2,False,False) Minimum (1,Tech213T_F,FP2,False,False) Minimum (1,RearMes215T_F,FP2,False,False) Minimum (1,MensRR217F_F,FP2,False,False) EndTable DataTable (FifteenMinPV,1,-1) DataInterval (0,15,Min,10) Sample (1,PV1VDC_VDC,FP2) Sample (1,PV2VDC_VDC,FP2) Sample (1,PV3VDC_VDC,FP2) Sample (1,PV4VDC_VDC,FP2) Sample (1,PV1Amps_A,FP2) Sample (1,PV2Amps_A,FP2) Sample (1,PV3Amps_A,FP2) Sample (1,PV4Amps_A,FP2) Sample (1,PV1Lo_kw,FP2) Sample (1,PV1Hi_kw,FP2) Sample (1,PV1Demand_kw,FP2) Sample (1,PV1PwrFac,FP2) Sample (1,PV1Current_A,FP2) Sample (1,PV2Lo_kw,FP2) Sample (1,PV2Hi_kw,FP2) Sample (1,PV2Demand_kw,FP2) Sample (1,PV2PwrFac,FP2) Sample (1,PV2Current_A,FP2) Sample (1,PV3Lo_kw,FP2) Sample (1,PV3Hi_kw,FP2) Sample (1,PV3Demand_kw,FP2) Sample (1,PV3PwrFac,FP2) Sample (1,PV3Current_A,FP2) Sample (1,PV4Lo_kw,FP2) Sample (1,PV4Hi_kw,FP2) Sample (1,PV4Demand_kw,FP2) Sample (1,PV4PwrFac,FP2) Sample (1,PV4Current_A,FP2) Average (1,PV1VDC_VDC,FP2,False) Average (1,PV2VDC_VDC,FP2,False) Average (1,PV3VDC_VDC,FP2,False) Average (1,PV4VDC_VDC,FP2,False) Average (1,PV1Amps_A,FP2,False) Average (1,PV2Amps_A,FP2,False) Average (1,PV3Amps_A,FP2,False) Average (1,PV4Amps_A,FP2,False) Average (1,PV1Lo_kw,FP2,False) Average (1,PV1Hi_kw,FP2,False) Average (1,PV1Demand_kw,FP2,False) Average (1,PV1PwrFac,FP2,False) Average (1,PV1Current_A,FP2,False) Average (1,PV2Lo_kw,FP2,False) Average (1,PV2Hi_kw,FP2,False) Average (1,PV2Demand_kw,FP2,False) Average (1,PV2PwrFac,FP2,False) Average (1,PV2Current_A,FP2,False) Average (1,PV3Lo_kw,FP2,False) Average (1,PV3Hi_kw,FP2,False) Average (1,PV3Demand_kw,FP2,False) Average (1,PV3PwrFac,FP2,False) Average (1,PV3Current_A,FP2,False) Average (1,PV4Lo_kw,FP2,False) Average (1,PV4Hi_kw,FP2,False) Average (1,PV4Demand_kw,FP2,False) Average (1,PV4PwrFac,FP2,False) Average (1,PV4Current_A,FP2,False) Maximum (1,PV1VDC_VDC,FP2,False,False) Maximum (1,PV2VDC_VDC,FP2,False,False) Maximum (1,PV3VDC_VDC,FP2,False,False) Maximum (1,PV4VDC_VDC,FP2,False,False) Maximum (1,PV1Amps_A,FP2,False,False) Maximum (1,PV2Amps_A,FP2,False,False) Maximum (1,PV3Amps_A,FP2,False,False) Maximum (1,PV4Amps_A,FP2,False,False) Maximum (1,BldgLo_kw,FP2,False,False) Maximum (1,BldgHi_kw,FP2,False,False) Maximum (1,BldgDemand_kw,FP2,False,False) Maximum (1,BldgPwrFac,FP2,False,False) Maximum (1,BldgCurrent_A,FP2,False,False) Maximum (1,PV1Lo_kw,FP2,False,False) Maximum (1,PV1Hi_kw,FP2,False,False) Maximum (1,PV1Demand_kw,FP2,False,False) Maximum (1,PV1PwrFac,FP2,False,False) Maximum (1,PV1Current_A,FP2,False,False) Maximum (1,PV2Lo_kw,FP2,False,False) Maximum (1,PV2Hi_kw,FP2,False,False) Maximum (1,PV2Demand_kw,FP2,False,False) Maximum (1,PV2PwrFac,FP2,False,False) Maximum (1,PV2Current_A,FP2,False,False) Maximum (1,PV3Lo_kw,FP2,False,False) Maximum (1,PV3Hi_kw,FP2,False,False) Maximum (1,PV3Demand_kw,FP2,False,False) Maximum (1,PV3PwrFac,FP2,False,False) Maximum (1,PV3Current_A,FP2,False,False) Maximum (1,PV4Lo_kw,FP2,False,False) Maximum (1,PV4Hi_kw,FP2,False,False) Maximum (1,PV4Demand_kw,FP2,False,False) Maximum (1,PV4PwrFac,FP2,False,False) Maximum (1,PV4Current_A,FP2,False,False) Minimum (1,PV1VDC_VDC,FP2,False,False) Minimum (1,PV2VDC_VDC,FP2,False,False) Minimum (1,PV3VDC_VDC,FP2,False,False) Minimum (1,PV4VDC_VDC,FP2,False,False) Minimum (1,PV1Amps_A,FP2,False,False) Minimum (1,PV2Amps_A,FP2,False,False) Minimum (1,PV3Amps_A,FP2,False,False) Minimum (1,PV4Amps_A,FP2,False,False) Minimum (1,BldgLo_kw,FP2,False,False) Minimum (1,BldgHi_kw,FP2,False,False) Minimum (1,BldgDemand_kw,FP2,False,False) Minimum (1,BldgPwrFac,FP2,False,False) Minimum (1,BldgCurrent_A,FP2,False,False) Minimum (1,PV1Lo_kw,FP2,False,False) Minimum (1,PV1Hi_kw,FP2,False,False) Minimum (1,PV1Demand_kw,FP2,False,False) Minimum (1,PV1PwrFac,FP2,False,False) Minimum (1,PV1Current_A,FP2,False,False) Minimum (1,PV2Lo_kw,FP2,False,False) Minimum (1,PV2Hi_kw,FP2,False,False) Minimum (1,PV2Demand_kw,FP2,False,False) Minimum (1,PV2PwrFac,FP2,False,False) Minimum (1,PV2Current_A,FP2,False,False) Minimum (1,PV3Lo_kw,FP2,False,False) Minimum (1,PV3Hi_kw,FP2,False,False) Minimum (1,PV3Demand_kw,FP2,False,False) Minimum (1,PV3PwrFac,FP2,False,False) Minimum (1,PV3Current_A,FP2,False,False) Minimum (1,PV4Lo_kw,FP2,False,False) Minimum (1,PV4Hi_kw,FP2,False,False) Minimum (1,PV4Demand_kw,FP2,False,False) Minimum (1,PV4PwrFac,FP2,False,False) Minimum (1,PV4Current_A,FP2,False,False) EndTable DataTable (FifteenMinDomWater,1,-1) DataInterval (0,15,Min,10) Sample (1,DomTank1Lvl_ft,FP2) Sample (1,DomTank2Lvl_ft,FP2 Average (1,DomTank1Lvl_ft,FP2,False) Average (1,DomTank2Lvl_ft,FP2,False) Maximum (1,DomTank1Lvl_ft,FP2,False,False) Maximum (1,DomTank2Lvl_ft,FP2,False,False) Minimum (1,DomTank1Lvl_ft,FP2,False,False) Minimum (1,DomTank2Lvl_ft,FP2,False,False) EndTable DataTable (FifteenMinSolDomHot,1,-1) DataInterval (0,15,Min,10) Sample (1,DomBTU_BTU_H,FP2) Sample (1,DomVol_GPH,FP2) Sample (1,DomST_F,FP2) Sample (1,DomRT_F,FP2) Sample (1,DomDT_F,FP2) Sample (1,DomTBTU_BTU,FP2) Sample (1,DomTankHWT_F,FP2) ' added 28May2009 AMcHugh Sample (1,HelioBTU_BTU_H,FP2) Sample (1,HelioVol_GPH,FP2) Sample (1,HelioST_F,FP2) Sample (1,HelioRT_F,FP2) Sample (1,HelioDT_F,FP2) Sample (1,HelioTBTU_BTU,FP2) Sample (1,HelioHDBTU_BTU_H,FP2) Sample (1,HelioHDVol_GPH,FP2) Sample (1,HelioHDST_F,FP2) Sample (1,HelioHDRT_F,FP2) Sample (1,HelioHDDT_F,FP2) Sample (1,HelioHDTBTU_BTU,FP2) Average (1,DomBTU_BTU_H,FP2,False) Average (1,DomVol_GPH,FP2,False) Average (1,DomST_F,FP2,False) Average (1,DomRT_F,FP2,False) Average (1,DomDT_F,FP2,False) Average (1,DomTBTU_BTU,FP2,False) Average (1,DomTankHWT_F,FP2,False) ' added 28May2009 AMcHugh Average (1,HelioBTU_BTU_H,FP2,False) Average (1,HelioVol_GPH,FP2,False) Average (1,HelioST_F,FP2,False) Average (1,HelioRT_F,FP2,False) Average (1,HelioDT_F,FP2,False) Average (1,HelioTBTU_BTU,FP2,False) Average (1,HelioHDBTU_BTU_H,FP2,False) Average (1,HelioHDVol_GPH,FP2,False) Average (1,HelioHDST_F,FP2,False) Average (1,HelioHDRT_F,FP2,False) Average (1,HelioHDDT_F,FP2,False) Average (1,HelioHDTBTU_BTU,FP2,False) Maximum (1,DomBTU_BTU_H,FP2,False,False) Maximum (1,DomVol_GPH,FP2,False,False) Maximum (1,DomST_F,FP2,False,False) Maximum (1,DomRT_F,FP2,False,False) Maximum (1,DomDT_F,FP2,False,False) Maximum (1,DomTBTU_BTU,FP2,False,False) Maximum (1,DomTankHWT_F,FP2,False,False) ' added 28May2009 AMcHugh Maximum (1,HelioBTU_BTU_H,FP2,False,False) Maximum (1,HelioVol_GPH,FP2,False,False) Maximum (1,HelioST_F,FP2,False,False) Maximum (1,HelioRT_F,FP2,False,False) Maximum (1,HelioDT_F,FP2,False,False) Maximum (1,HelioTBTU_BTU,FP2,False,False) Maximum (1,HelioHDBTU_BTU_H,FP2,False,False) Maximum (1,HelioHDVol_GPH,FP2,False,False) Maximum (1,HelioHDST_F,FP2,False,False) Maximum (1,HelioHDRT_F,FP2,False,False) Maximum (1,HelioHDDT_F,FP2,False,False) Maximum (1,HelioHDTBTU_BTU,FP2,False,False) Minimum (1,DomBTU_BTU_H,FP2,False,False) Minimum (1,DomVol_GPH,FP2,False,False) Minimum (1,DomST_F,FP2,False,False) Minimum (1,DomRT_F,FP2,False,False) Minimum (1,DomDT_F,FP2,False,False) Minimum (1,DomTBTU_BTU,FP2,False,False) Minimum (1,DomTankHWT_F,FP2,False,False) ' added 28May2009 AMcHugh Minimum (1,HelioBTU_BTU_H,FP2,False,False) Minimum (1,HelioVol_GPH,FP2,False,False) Minimum (1,HelioST_F,FP2,False,False) Minimum (1,HelioRT_F,FP2,False,False) Minimum (1,HelioDT_F,FP2,False,False) Minimum (1,HelioTBTU_BTU,FP2,False,False) Minimum (1,HelioHDBTU_BTU_H,FP2,False,False) Minimum (1,HelioHDVol_GPH,FP2,False,False) Minimum (1,HelioHDST_F,FP2,False,False) Minimum (1,HelioHDRT_F,FP2,False,False) Minimum (1,HelioHDDT_F,FP2,False,False) Minimum (1,HelioHDTBTU_BTU,FP2,False,False) EndTable DataTable (FifteenMinSolHydrnc,1,-1) DataInterval (0,15,Min,10) Sample (1,RadTankBTU_BTU_H,FP2) Sample (1,RadTankVol_GPH,FP2) Sample (1,RadTankST_F,FP2) Sample (1,RadTankRT_F,FP2) Sample (1,RadTankDT_F,FP2) Sample (1,RadTankTBTU_BTU,FP2) Sample (1,TMaxHDBTU_BTU_H,FP2) Sample (1,TMaxHDVol_GPH,FP2) Sample (1,TMaxHDST_F,FP2) Sample (1,TMaxHDRT_F,FP2) Sample (1,TMaxHDDT_F,FP2) Sample (1,TMaxHDTBTU_BTU,FP2) Sample (1,TMaxBTU_BTU_H,FP2) Sample (1,TMaxVol_GPH,FP2) Sample (1,TMaxST_F,FP2) Sample (1,TMaxRT_F,FP2) Sample (1,TMaxDT_F,FP2) Sample (1,TMaxTBTU_BTU,FP2) Sample (1,TMaxHWT_F,FP2) ' added 29May2009 AMcHugh Sample (1,RadTankHWT_F,FP2) ' added 29May2009 AMcHugh Average (1,RadTankBTU_BTU_H,FP2,False) Average (1,RadTankVol_GPH,FP2,False) Average (1,RadTankST_F,FP2,False) Average (1,RadTankRT_F,FP2,False) Average (1,RadTankDT_F,FP2,False Average (1,RadTankTBTU_BTU,FP2,False) Average (1,TMaxHDBTU_BTU_H,FP2,False) Average (1,TMaxHDVol_GPH,FP2,False) Average (1,TMaxHDST_F,FP2,False) Average (1,TMaxHDRT_F,FP2,False) Average (1,TMaxHDDT_F,FP2,False) Average (1,TMaxHDTBTU_BTU,FP2,False) Average (1,TMaxBTU_BTU_H,FP2,False) Average (1,TMaxVol_GPH,FP2,False) Average (1,TMaxST_F,FP2,False) Average (1,TMaxRT_F,FP2,False) Average (1,TMaxDT_F,FP2,False) Average (1,TMaxTBTU_BTU,FP2,False) Average (1,TMaxHWT_F,FP2,False) ' added 29May2009 AMcHugh Average (1,RadTankHWT_F,FP2,False) ' added 29May2009 AMcHugh Maximum (1,RadTankBTU_BTU_H,FP2,False,False) Maximum (1,RadTankVol_GPH,FP2,False,False) Maximum (1,RadTankST_F,FP2,False,False) Maximum (1,RadTankRT_F,FP2,False,False) Maximum (1,RadTankDT_F,FP2,False,False) Maximum (1,RadTankTBTU_BTU,FP2,False,False) Maximum (1,TMaxHDBTU_BTU_H,FP2,False,False) Maximum (1,TMaxHDVol_GPH,FP2,False,False) Maximum (1,TMaxHDST_F,FP2,False,False) Maximum (1,TMaxHDRT_F,FP2,False,False) Maximum (1,TMaxHDDT_F,FP2,False,False) Maximum (1,TMaxHDTBTU_BTU,FP2,False,False) Maximum (1,TMaxBTU_BTU_H,FP2,False,False) Maximum (1,TMaxVol_GPH,FP2,False,False) Maximum (1,TMaxST_F,FP2,False,False) Maximum (1,TMaxRT_F,FP2,False,False) Maximum (1,TMaxDT_F,FP2,False,False) Maximum (1,TMaxTBTU_BTU,FP2,False,False) Maximum (1,TMaxHWT_F,FP2,False,False) ' added 28May2009 AMcHugh Maximum (1,RadTankHWT_F,FP2,False,False) ' added 28May2009 AMcHugh Minimum (1,RadTankBTU_BTU_H,FP2,False,False) Minimum (1,RadTankVol_GPH,FP2,False,False) Minimum (1,RadTankST_F,FP2,False,False) Minimum (1,RadTankRT_F,FP2,False,False) Minimum (1,RadTankDT_F,FP2,False,False) Minimum (1,RadTankTBTU_BTU,FP2,False,False) Minimum (1,TMaxHDBTU_BTU_H,FP2,False,False) Minimum (1,TMaxHDVol_GPH,FP2,False,False) Minimum (1,TMaxHDST_F,FP2,False,False) Minimum (1,TMaxHDRT_F,FP2,False,False) Minimum (1,TMaxHDDT_F,FP2,False,False) Minimum (1,TMaxHDTBTU_BTU,FP2,False,False) Minimum (1,TMaxBTU_BTU_H,FP2,False,False) Minimum (1,TMaxVol_GPH,FP2,False,False) Minimum (1,TMaxST_F,FP2,False,False) Minimum (1,TMaxRT_F,FP2,False,False) Minimum (1,TMaxDT_F,FP2,False,False) Minimum (1,TMaxTBTU_BTU,FP2,False,False) Minimum (1,TMaxHWT_F,FP2,False,False) ' added 28May2009 AMcHugh Minimum (1,RadTankHWT_F,FP2,False,False) ' added 28May2009 AMcHugh EndTable DataTable (FifteenMinEnergyCon,1,-1) DataInterval (0,15,Min,10) Sample (1,BldgLo_kw,FP2) Sample (1,BldgHi_kw,FP2) Sample (1,BldgDemand_kw,FP2) Sample (1,BldgPwrFac,FP2) Sample (1,BldgCurrent_A,FP2) Average (1,BldgLo_kw,FP2,False) Average (1,BldgHi_kw,FP2,False) Average (1,BldgDemand_kw,FP2,False) Average (1,BldgPwrFac,FP2,False) Average (1,BldgCurrent_A,FP2,False) Maximum (1,BldgLo_kw,FP2,False,False) Maximum (1,BldgHi_kw,FP2,False,False) Maximum (1,BldgDemand_kw,FP2,False,False) Maximum (1,BldgPwrFac,FP2,False,False) Maximum (1,BldgCurrent_A,FP2,False,False) Minimum (1,BldgLo_kw,FP2,False,False) Minimum (1,BldgHi_kw,FP2,False,False) Minimum (1,BldgDemand_kw,FP2,False,False) Minimum (1,BldgPwrFac,FP2,False,False) Minimum (1,BldgCurrent_A,FP2,False,False) Sample (1,QuarterHrUsage_kw,FP2) ' this is the computed Usage EndTable 'Hourly tables DataTable (HourlyRadHeat,True,-1) DataInterval (0,60,Min,10) Sample (1,Blr1Fuel_G,FP2) Sample (1,BlrSupTemp_F,FP2) Sample (1,BlrRetTemp_F,FP2) Sample (1,Blr1Stack_F,FP2) Sample (1,BLR1BTU_BTU_H,FP2) Sample (1,BLR1Vol_GPM,FP2) Sample (1,BLR1ST_F,FP2) Sample (1,BLR1RT_F,FP2) Sample (1,BLR1DT_F,FP2) Sample (1,BLR1TBTU_BTU,FP2) Average (1,Blr1Fuel_G,FP2,False) Average (1,BlrSupTemp_F,FP2,False) Average (1,BlrRetTemp_F,FP2,False) Average (1,Blr1Stack_F,FP2,False) Average (1,BLR1BTU_BTU_H,FP2,False) Average (1,BLR1Vol_GPM,FP2,False) Average (1,BLR1ST_F,FP2,False) Average (1,BLR1RT_F,FP2,False) Average (1,BLR1DT_F,FP2,False) Average (1,BLR1TBTU_BTU,FP2,False) Maximum (1,Blr1Fuel_G,FP2,False,False) Maximum (1,BlrSupTemp_F,FP2,False,False) Maximum (1,BlrRetTemp_F,FP2,False,False) Maximum (1,Blr1Stack_F,FP2,False,False) Maximum (1,BLR1BTU_BTU_H,FP2,False,False) Maximum (1,BLR1Vol_GPM,FP2,False,False) Maximum (1,BLR1ST_F,FP2,False,False) Maximum (1,BLR1RT_F,FP2,False,False) Maximum (1,BLR1DT_F,FP2,False,False) Maximum (1,BLR1TBTU_BTU,FP2,False,False) Minimum (1,Blr1Fuel_G,FP2,False,False) Minimum (1,BlrSupTemp_F,FP2,False,False) Minimum (1,BlrRetTemp_F,FP2,False,False) Minimum (1,Blr1Stack_F,FP2,False,False) Minimum (1,BLR1BTU_BTU_H,FP2,False,False) Minimum (1,BLR1Vol_GPM,FP2,False,False) Minimum (1,BLR1ST_F,FP2,False,False) Minimum (1,BLR1RT_F,FP2,False,False) Minimum (1,BLR1DT_F,FP2,False,False) Minimum (1,BLR1TBTU_BTU,FP2,False,False) EndTable DataTable (HourlyBsmntLabHt,1,-1) DataInterval (0,60,Min,10) Sample (1,Blr2Fuel_G,FP2) Sample (1,Blr3Fuel_G,FP2) Sample (1,Blr2Stack_F,FP2) Sample (1,Blr3Stack_F,FP2) Sample (1,BLR2BTU_BTU_H,FP2) Sample (1,BLR2Vol_GPM,FP2) Sample (1,BLR2ST_F,FP2) Sample (1,BLR2RT_F,FP2) Sample (1,BLR2DT_F,FP2) Sample (1,BLR2TBTU_BTU,FP2) Sample (1,BLR3BTU_BTU_H,FP2) Sample (1,BLR3Vol_GPM,FP2) Sample (1,BLR3ST_F,FP2) Sample (1,BLR3RT_F,FP2) Sample (1,BLR3DT_F,FP2) Sample (1,BLR3TBTU_BTU,FP2) Average (1,Blr2Fuel_G,FP2,False) Average (1,Blr3Fuel_G,FP2,False) Average (1,Blr2Stack_F,FP2,False) Average (1,Blr3Stack_F,FP2,False) Average (1,BLR2BTU_BTU_H,FP2,False) Average (1,BLR2Vol_GPM,FP2,False) Average (1,BLR2ST_F,FP2,False) Average (1,BLR2RT_F,FP2,False) Average (1,BLR2DT_F,FP2,False) Average (1,BLR2TBTU_BTU,FP2,False) Average (1,BLR3BTU_BTU_H,FP2,False) Average (1,BLR3Vol_GPM,FP2,False) Average (1,BLR3ST_F,FP2,False) Average (1,BLR3RT_F,FP2,False) Average (1,BLR3DT_F,FP2,False) Average (1,BLR3TBTU_BTU,FP2,False) Maximum (1,Blr2Fuel_G,FP2,False,False) Maximum (1,Blr3Fuel_G,FP2,False,False) Maximum (1,Blr2Stack_F,FP2,False,False) Maximum (1,Blr3Stack_F,FP2,False,False) Maximum (1,BLR2BTU_BTU_H,FP2,False,False) Maximum (1,BLR2Vol_GPM,FP2,False,False) Maximum (1,BLR2ST_F,FP2,False,False) Maximum (1,BLR2RT_F,FP2,False,False) Maximum (1,BLR2DT_F,FP2,False,False) Maximum (1,BLR2TBTU_BTU,FP2,False,False) Maximum (1,BLR3BTU_BTU_H,FP2,False,False) Maximum (1,BLR3Vol_GPM,FP2,False,False) Maximum (1,BLR3ST_F,FP2,False,False) Maximum (1,BLR3RT_F,FP2,False,False) Maximum (1,BLR3DT_F,FP2,False,False) Maximum (1,BLR3TBTU_BTU,FP2,False,False) Minimum (1,Blr2Fuel_G,FP2,False,False) Minimum (1,Blr3Fuel_G,FP2,False,False) Minimum (1,Blr2Stack_F,FP2,False,False) Minimum (1,Blr3Stack_F,FP2,False,False) Minimum (1,BLR2BTU_BTU_H,FP2,False,False) Minimum (1,BLR2Vol_GPM,FP2,False,False) Minimum (1,BLR2ST_F,FP2,False,False) Minimum (1,BLR2RT_F,FP2,False,False) Minimum (1,BLR2DT_F,FP2,False,False) Minimum (1,BLR2TBTU_BTU,FP2,False,False) Minimum (1,BLR3BTU_BTU_H,FP2,False,False) Minimum (1,BLR3Vol_GPM,FP2,False,False) Minimum (1,BLR3ST_F,FP2,False,False) Minimum (1,BLR3RT_F,FP2,False,False) Minimum (1,BLR3DT_F,FP2,False,False) Minimum (1,BLR3TBTU_BTU,FP2,False,False) EndTable DataTable (HourlyEnv,1,-1) DataInterval (0,60,Min,10) Sample (1,OAT_F,FP2) Sample (1,OAH_Pct,FP2) Sample (1,HRV1CO2_ppm,FP2) Sample (1,HRV1RMT_F,FP2) Sample (1,HRV1RMH_Pct,FP2) Sample (1,HRV21CO2_ppm,FP2) Sample (1,HRV21RMT_F,FP2) Sample (1,HRV21RMH_pct,FP2) Sample (1,HRV22CO2_ppm,FP2) Sample (1,HRV22RMT_F,FP2) Sample (1,HRV22RMH_pct,FP2) Sample (1,HRV2SAT_F,FP2) Sample (1,HRV3SAT_F,FP2) Sample (1,HRV3CO2_ppm,FP2) Sample (1,HRV42RMT_F,FP2) Sample (1,HRV41RMH_pct,FP2) Sample (1,HRV4SAT_F,FP2) Sample (1,OACO2_ppm,FP2) Sample (1,HRV5CO2_ppm,FP2) Sample (1,HRV5RMT_F,FP2) Sample (1,HRV5RMH_pct,FP2) Sample (1,HRV5SAT_F,FP2) Sample (1,HRV5RAT_F,FP2) Sample (1,HRV5MAD_pct,FP2) Sample (1,Stair05T_F,FP2) Sample (1,Elev07T_F,FP2) Sample (1,Stair111T_F,FP2) Sample (1,Elev112T_F,FP2) Sample (1,SLOffice116T_F,FP2) Sample (1,BackDoor117T_F,FP2) Sample (1,Elev210T_F,FP2) Sample (1,FrontMes211T_F,FP2) Sample (1,Tech213T_F,FP2) Sample (1,RearMes215T_F,FP2) Sample (1,MensRR217F_F,FP2) Average (1,OAT_F,FP2,False) Average (1,OAH_Pct,FP2,False) Average (1,HRV1CO2_ppm,FP2,False) Average (1,HRV1RMT_F,FP2,False) Average (1,HRV1RMH_Pct,FP2,False) Average (1,HRV21CO2_ppm,FP2,False) Average (1,HRV21RMT_F,FP2,False) Average (1,HRV21RMH_pct,FP2,False) Average (1,HRV22CO2_ppm,FP2,False) Average (1,HRV22RMT_F,FP2,False) Average (1,HRV22RMH_pct,FP2,False) Average (1,HRV2SAT_F,FP2,False) Average (1,HRV3SAT_F,FP2,False) Average (1,HRV3CO2_ppm,FP2,False) Average (1,HRV42RMT_F,FP2,False) Average (1,HRV41RMH_pct,FP2,False) Average (1,HRV4SAT_F,FP2,False) Average (1,OACO2_ppm,FP2,False) Average (1,HRV5CO2_ppm,FP2,False) Average (1,HRV5RMT_F,FP2,False) Average (1,HRV5RMH_pct,FP2,False) Average (1,HRV5SAT_F,FP2,False) Average (1,HRV5RAT_F,FP2,False) Average (1,HRV5MAD_pct,FP2,False) Average (1,Stair05T_F,FP2,False) Average (1,Elev07T_F,FP2,False) Average (1,Stair111T_F,FP2,False) Average (1,Elev112T_F,FP2,False) Average (1,SLOffice116T_F,FP2,False) Average (1,BackDoor117T_F,FP2,False) Average (1,Elev210T_F,FP2,False) Average (1,FrontMes211T_F,FP2,False) Average (1,Tech213T_F,FP2,False) Average (1,RearMes215T_F,FP2,False) Average (1,MensRR217F_F,FP2,False) Maximum (1,OAT_F,FP2,False,False) Maximum (1,OAH_Pct,FP2,False,False) Maximum (1,HRV1CO2_ppm,FP2,False,False) Maximum (1,HRV1RMT_F,FP2,False,False) Maximum (1,HRV1RMH_Pct,FP2,False,False) Maximum (1,HRV21CO2_ppm,FP2,False,False) Maximum (1,HRV21RMT_F,FP2,False,False) Maximum (1,HRV21RMH_pct,FP2,False,False) Maximum (1,HRV22CO2_ppm,FP2,False,False) Maximum (1,HRV22RMT_F,FP2,False,False) Maximum (1,HRV22RMH_pct,FP2,False,False) Maximum (1,HRV2SAT_F,FP2,False,False) Maximum (1,HRV3SAT_F,FP2,False,False) Maximum (1,HRV3CO2_ppm,FP2,False,False) Maximum (1,HRV42RMT_F,FP2,False,False) Maximum (1,HRV41RMH_pct,FP2,False,False) Maximum (1,HRV4SAT_F,FP2,False,False) Maximum (1,OACO2_ppm,FP2,False,False) Maximum (1,HRV5CO2_ppm,FP2,False,False) Maximum (1,HRV5RMT_F,FP2,False,False) Maximum (1,HRV5RMH_pct,FP2,False,False) Maximum (1,HRV5SAT_F,FP2,False,False) Maximum (1,HRV5RAT_F,FP2,False,False) Maximum (1,HRV5MAD_pct,FP2,False,False) Maximum (1,Stair05T_F,FP2,False,False) Maximum (1,Elev07T_F,FP2,False,False) Maximum (1,Stair111T_F,FP2,False,False) Maximum (1,Elev112T_F,FP2,False,False) Maximum (1,SLOffice116T_F,FP2,False,False) Maximum (1,BackDoor117T_F,FP2,False,False) Maximum (1,Elev210T_F,FP2,False,False) Maximum (1,FrontMes211T_F,FP2,False,False) Maximum (1,Tech213T_F,FP2,False,False) Maximum (1,RearMes215T_F,FP2,False,False) Maximum (1,MensRR217F_F,FP2,False,False) Minimum (1,OAT_F,FP2,False,False) Minimum (1,OAH_Pct,FP2,False,False) Minimum (1,HRV1CO2_ppm,FP2,False,False) Minimum (1,HRV1RMT_F,FP2,False,False) Minimum (1,HRV1RMH_Pct,FP2,False,False) Minimum (1,HRV21CO2_ppm,FP2,False,False) Minimum (1,HRV21RMT_F,FP2,False,False) Minimum (1,HRV21RMH_pct,FP2,False,False) Minimum (1,HRV22CO2_ppm,FP2,False,False) Minimum (1,HRV22RMT_F,FP2,False,False) Minimum (1,HRV22RMH_pct,FP2,False,False) Minimum (1,HRV2SAT_F,FP2,False,False) Minimum (1,HRV3SAT_F,FP2,False,False) Minimum (1,HRV3CO2_ppm,FP2,False,False) Minimum (1,HRV42RMT_F,FP2,False,False) Minimum (1,HRV41RMH_pct,FP2,False,False) Minimum (1,HRV4SAT_F,FP2,False,False) Minimum (1,OACO2_ppm,FP2,False,False) Minimum (1,HRV5CO2_ppm,FP2,False,False) Minimum (1,HRV5RMT_F,FP2,False,False) Minimum (1,HRV5RMH_pct,FP2,False,False) Minimum (1,HRV5SAT_F,FP2,False,False) Minimum (1,HRV5RAT_F,FP2,False,False) Minimum (1,HRV5MAD_pct,FP2,False,False) Minimum (1,Stair05T_F,FP2,False,False) Minimum (1,Elev07T_F,FP2,False,False) Minimum (1,Stair111T_F,FP2,False,False) Minimum (1,Elev112T_F,FP2,False,False) Minimum (1,SLOffice116T_F,FP2,False,False) Minimum (1,BackDoor117T_F,FP2,False,False) Minimum (1,Elev210T_F,FP2,False,False) Minimum (1,FrontMes211T_F,FP2,False,False) Minimum (1,Tech213T_F,FP2,False,False) Minimum (1,RearMes215T_F,FP2,False,False) Minimum (1,MensRR217F_F,FP2,False,False) EndTable DataTable (HourlyPV,1,-1) DataInterval (0,60,Min,10) Sample (1,PV1VDC_VDC,FP2) Sample (1,PV2VDC_VDC,FP2) Sample (1,PV3VDC_VDC,FP2) Sample (1,PV4VDC_VDC,FP2) Sample (1,PV1Amps_A,FP2) Sample (1,PV2Amps_A,FP2) Sample (1,PV3Amps_A,FP2) Sample (1,PV4Amps_A,FP2) Sample (1,PV1Lo_kw,FP2) Sample (1,PV1Hi_kw,FP2) Sample (1,PV1Demand_kw,FP2) Sample (1,PV1PwrFac,FP2) Sample (1,PV1Current_A,FP2) Sample (1,PV2Lo_kw,FP2) Sample (1,PV2Hi_kw,FP2) Sample (1,PV2Demand_kw,FP2) Sample (1,PV2PwrFac,FP2) Sample (1,PV2Current_A,FP2) Sample (1,PV3Lo_kw,FP2) Sample (1,PV3Hi_kw,FP2) Sample (1,PV3Demand_kw,FP2) Sample (1,PV3PwrFac,FP2) Sample (1,PV3Current_A,FP2) Sample (1,PV4Lo_kw,FP2) Sample (1,PV4Hi_kw,FP2) Sample (1,PV4Demand_kw,FP2) Sample (1,PV4PwrFac,FP2) Sample (1,PV4Current_A,FP2) Average (1,PV1VDC_VDC,FP2,False) Average (1,PV2VDC_VDC,FP2,False) Average (1,PV3VDC_VDC,FP2,False) Average (1,PV4VDC_VDC,FP2,False) Average (1,PV1Amps_A,FP2,False) Average (1,PV2Amps_A,FP2,False) Average (1,PV3Amps_A,FP2,False) Average (1,PV4Amps_A,FP2,False) Average (1,PV1Lo_kw,FP2,False) Average (1,PV1Hi_kw,FP2,False) Average (1,PV1Demand_kw,FP2,False) Average (1,PV1PwrFac,FP2,False) Average (1,PV1Current_A,FP2,False) Average (1,PV2Lo_kw,FP2,False) Average (1,PV2Hi_kw,FP2,False) Average (1,PV2Demand_kw,FP2,False) Average (1,PV2PwrFac,FP2,False) Average (1,PV2Current_A,FP2,False) Average (1,PV3Lo_kw,FP2,False) Average (1,PV3Hi_kw,FP2,False) Average (1,PV3Demand_kw,FP2,False) Average (1,PV3PwrFac,FP2,False) Average (1,PV3Current_A,FP2,False) Average (1,PV4Lo_kw,FP2,False) Average (1,PV4Hi_kw,FP2,False) Average (1,PV4Demand_kw,FP2,False) Average (1,PV4PwrFac,FP2,False) Average (1,PV4Current_A,FP2,False) Maximum (1,PV1VDC_VDC,FP2,False,False) Maximum (1,PV2VDC_VDC,FP2,False,False) Maximum (1,PV3VDC_VDC,FP2,False,False) Maximum (1,PV4VDC_VDC,FP2,False,False) Maximum (1,PV1Amps_A,FP2,False,False) Maximum (1,PV2Amps_A,FP2,False,False) Maximum (1,PV3Amps_A,FP2,False,False) Maximum (1,PV4Amps_A,FP2,False,False) Maximum (1,BldgLo_kw,FP2,False,False) Maximum (1,BldgHi_kw,FP2,False,False) Maximum (1,BldgDemand_kw,FP2,False,False) Maximum (1,BldgPwrFac,FP2,False,False) Maximum (1,BldgCurrent_A,FP2,False,False) Maximum (1,PV1Lo_kw,FP2,False,False) Maximum (1,PV1Hi_kw,FP2,False,False) Maximum (1,PV1Demand_kw,FP2,False,False) Maximum (1,PV1PwrFac,FP2,False,False) Maximum (1,PV1Current_A,FP2,False,False) Maximum (1,PV2Lo_kw,FP2,False,False) Maximum (1,PV2Hi_kw,FP2,False,False) Maximum (1,PV2Demand_kw,FP2,False,False) Maximum (1,PV2PwrFac,FP2,False,False) Maximum (1,PV2Current_A,FP2,False,False) Maximum (1,PV3Lo_kw,FP2,False,False) Maximum (1,PV3Hi_kw,FP2,False,False) Maximum (1,PV3Demand_kw,FP2,False,False) Maximum (1,PV3PwrFac,FP2,False,False) Maximum (1,PV3Current_A,FP2,False,False) Maximum (1,PV4Lo_kw,FP2,False,False) Maximum (1,PV4Hi_kw,FP2,False,False) Maximum (1,PV4Demand_kw,FP2,False,False) Maximum (1,PV4PwrFac,FP2,False,False) Maximum (1,PV4Current_A,FP2,False,False) Minimum (1,PV1VDC_VDC,FP2,False,False) Minimum (1,PV2VDC_VDC,FP2,False,False) Minimum (1,PV3VDC_VDC,FP2,False,False) Minimum (1,PV4VDC_VDC,FP2,False,False) Minimum (1,PV1Amps_A,FP2,False,False) Minimum (1,PV2Amps_A,FP2,False,False) Minimum (1,PV3Amps_A,FP2,False,False) Minimum (1,PV4Amps_A,FP2,False,False) Minimum (1,BldgLo_kw,FP2,False,False) Minimum (1,BldgHi_kw,FP2,False,False) Minimum (1,BldgDemand_kw,FP2,False,False) Minimum (1,BldgPwrFac,FP2,False,False) Minimum (1,BldgCurrent_A,FP2,False,False) Minimum (1,PV1Lo_kw,FP2,False,False) Minimum (1,PV1Hi_kw,FP2,False,False) Minimum (1,PV1Demand_kw,FP2,False,False) Minimum (1,PV1PwrFac,FP2,False,False) Minimum (1,PV1Current_A,FP2,False,False) Minimum (1,PV2Lo_kw,FP2,False,False) Minimum (1,PV2Hi_kw,FP2,False,False) Minimum (1,PV2Demand_kw,FP2,False,False) Minimum (1,PV2PwrFac,FP2,False,False) Minimum (1,PV2Current_A,FP2,False,False) Minimum (1,PV3Lo_kw,FP2,False,False) Minimum (1,PV3Hi_kw,FP2,False,False) Minimum (1,PV3Demand_kw,FP2,False,False) Minimum (1,PV3PwrFac,FP2,False,False) Minimum (1,PV3Current_A,FP2,False,False) Minimum (1,PV4Lo_kw,FP2,False,False) Minimum (1,PV4Hi_kw,FP2,False,False) Minimum (1,PV4Demand_kw,FP2,False,False) Minimum (1,PV4PwrFac,FP2,False,False) Minimum (1,PV4Current_A,FP2,False,False) EndTable DataTable (HourlyDomWater,1,-1) DataInterval (0,60,Min,10) Sample (1,DomTank1Lvl_ft,FP2) Sample (1,DomTank2Lvl_ft,FP2) Average (1,DomTank1Lvl_ft,FP2,False) Average (1,DomTank2Lvl_ft,FP2,False) Maximum (1,DomTank1Lvl_ft,FP2,False,False) Maximum (1,DomTank2Lvl_ft,FP2,False,False) Minimum (1,DomTank1Lvl_ft,FP2,False,False) Minimum (1,DomTank2Lvl_ft,FP2,False,False) EndTable DataTable (HourlySolDomHot,1,-1) DataInterval (0,60,Min,10) Sample (1,DomBTU_BTU_H,FP2) Sample (1,DomVol_GPH,FP2) Sample (1,DomST_F,FP2) Sample (1,DomRT_F,FP2) Sample (1,DomDT_F,FP2) Sample (1,DomTBTU_BTU,FP2) Sample (1,DomTankHWT_F,FP2) ' added 28May2009 AMcHugh Sample (1,HelioBTU_BTU_H,FP2) Sample (1,HelioVol_GPH,FP2) Sample (1,HelioST_F,FP2) Sample (1,HelioRT_F,FP2) Sample (1,HelioDT_F,FP2) Sample (1,HelioTBTU_BTU,FP2) Sample (1,HelioHDBTU_BTU_H,FP2) Sample (1,HelioHDVol_GPH,FP2) Sample (1,HelioHDST_F,FP2) Sample (1,HelioHDRT_F,FP2) Sample (1,HelioHDDT_F,FP2) Sample (1,HelioHDTBTU_BTU,FP2) Average (1,DomBTU_BTU_H,FP2,False) Average (1,DomVol_GPH,FP2,False) Average (1,DomST_F,FP2,False) Average (1,DomRT_F,FP2,False) Average (1,DomDT_F,FP2,False) Average (1,DomTBTU_BTU,FP2,False) Average (1,DomTankHWT_F,FP2,False) ' added 28May2009 AMcHugh Average (1,HelioBTU_BTU_H,FP2,False) Average (1,HelioVol_GPH,FP2,False) Average (1,HelioST_F,FP2,False) Average (1,HelioRT_F,FP2,False) Average (1,HelioDT_F,FP2,False) Average (1,HelioTBTU_BTU,FP2,False) Average (1,HelioHDBTU_BTU_H,FP2,False) Average (1,HelioHDVol_GPH,FP2,False) Average (1,HelioHDST_F,FP2,False) Average (1,HelioHDRT_F,FP2,False) Average (1,HelioHDDT_F,FP2,False) Average (1,HelioHDTBTU_BTU,FP2,False) Maximum (1,DomBTU_BTU_H,FP2,False,False) Maximum (1,DomVol_GPH,FP2,False,False) Maximum (1,DomST_F,FP2,False,False) Maximum (1,DomRT_F,FP2,False,False) Maximum (1,DomDT_F,FP2,False,False) Maximum (1,DomTBTU_BTU,FP2,False,False) Maximum (1,DomTankHWT_F,FP2,False,False) ' added 28May2009 AMcHugh Maximum (1,HelioBTU_BTU_H,FP2,False,False) Maximum (1,HelioVol_GPH,FP2,False,False) Maximum (1,HelioST_F,FP2,False,False) Maximum (1,HelioRT_F,FP2,False,False) Maximum (1,HelioDT_F,FP2,False,False) Maximum (1,HelioTBTU_BTU,FP2,False,False) Maximum (1,HelioHDBTU_BTU_H,FP2,False,False) Maximum (1,HelioHDVol_GPH,FP2,False,False) Maximum (1,HelioHDST_F,FP2,False,False) Maximum (1,HelioHDRT_F,FP2,False,False) Maximum (1,HelioHDDT_F,FP2,False,False) Maximum (1,HelioHDTBTU_BTU,FP2,False,False) Minimum (1,DomBTU_BTU_H,FP2,False,False) Minimum (1,DomVol_GPH,FP2,False,False) Minimum (1,DomST_F,FP2,False,False) Minimum (1,DomRT_F,FP2,False,False) Minimum (1,DomDT_F,FP2,False,False) Minimum (1,DomTBTU_BTU,FP2,False,False) Minimum (1,DomTankHWT_F,FP2,False,False) ' added 28May2009 AMcHugh Minimum (1,HelioBTU_BTU_H,FP2,False,False) Minimum (1,HelioVol_GPH,FP2,False,False) Minimum (1,HelioST_F,FP2,False,False) Minimum (1,HelioRT_F,FP2,False,False) Minimum (1,HelioDT_F,FP2,False,False) Minimum (1,HelioTBTU_BTU,FP2,False,False) Minimum (1,HelioHDBTU_BTU_H,FP2,False,False) Minimum (1,HelioHDVol_GPH,FP2,False,False) Minimum (1,HelioHDST_F,FP2,False,False) Minimum (1,HelioHDRT_F,FP2,False,False) Minimum (1,HelioHDDT_F,FP2,False,False) Minimum (1,HelioHDTBTU_BTU,FP2,False,False) EndTable DataTable (HourlySolHydrnc,1,-1) DataInterval (0,60,Min,10) Sample (1,RadTankBTU_BTU_H,FP2) Sample (1,RadTankVol_GPH,FP2) Sample (1,RadTankST_F,FP2) Sample (1,RadTankRT_F,FP2) Sample (1,RadTankDT_F,FP2) Sample (1,RadTankTBTU_BTU,FP2) Sample (1,TMaxHDBTU_BTU_H,FP2) Sample (1,TMaxHDVol_GPH,FP2) Sample (1,TMaxHDST_F,FP2) Sample (1,TMaxHDRT_F,FP2) Sample (1,TMaxHDDT_F,FP2) Sample (1,TMaxHDTBTU_BTU,FP2) Sample (1,TMaxBTU_BTU_H,FP2) Sample (1,TMaxVol_GPH,FP2) Sample (1,TMaxST_F,FP2) Sample (1,TMaxRT_F,FP2) Sample (1,TMaxDT_F,FP2) Sample (1,TMaxTBTU_BTU,FP2) Sample (1,TMaxHWT_F,FP2) ' added 29May2009 AMcHugh Sample (1,RadTankHWT_F,FP2) ' added 29May2009 AMcHugh Average (1,RadTankBTU_BTU_H,FP2,False) Average (1,RadTankVol_GPH,FP2,False) Average (1,RadTankST_F,FP2,False) Average (1,RadTankRT_F,FP2,False) Average (1,RadTankDT_F,FP2,False Average (1,RadTankTBTU_BTU,FP2,False) Average (1,TMaxHDBTU_BTU_H,FP2,False) Average (1,TMaxHDVol_GPH,FP2,False) Average (1,TMaxHDST_F,FP2,False) Average (1,TMaxHDRT_F,FP2,False) Average (1,TMaxHDDT_F,FP2,False) Average (1,TMaxHDTBTU_BTU,FP2,False) Average (1,TMaxBTU_BTU_H,FP2,False) Average (1,TMaxVol_GPH,FP2,False) Average (1,TMaxST_F,FP2,False) Average (1,TMaxRT_F,FP2,False) Average (1,TMaxDT_F,FP2,False) Average (1,TMaxTBTU_BTU,FP2,False) Average (1,TMaxHWT_F,FP2,False) ' added 29May2009 AMcHugh Average (1,RadTankHWT_F,FP2,False) ' added 29May2009 AMcHugh Maximum (1,RadTankBTU_BTU_H,FP2,False,False) Maximum (1,RadTankVol_GPH,FP2,False,False) Maximum (1,RadTankST_F,FP2,False,False) Maximum (1,RadTankRT_F,FP2,False,False) Maximum (1,RadTankDT_F,FP2,False,False) Maximum (1,RadTankTBTU_BTU,FP2,False,False) Maximum (1,TMaxHDBTU_BTU_H,FP2,False,False) Maximum (1,TMaxHDVol_GPH,FP2,False,False) Maximum (1,TMaxHDST_F,FP2,False,False) Maximum (1,TMaxHDRT_F,FP2,False,False) Maximum (1,TMaxHDDT_F,FP2,False,False) Maximum (1,TMaxHDTBTU_BTU,FP2,False,False) Maximum (1,TMaxBTU_BTU_H,FP2,False,False) Maximum (1,TMaxVol_GPH,FP2,False,False) Maximum (1,TMaxST_F,FP2,False,False) Maximum (1,TMaxRT_F,FP2,False,False) Maximum (1,TMaxDT_F,FP2,False,False) Maximum (1,TMaxTBTU_BTU,FP2,False,False) Maximum (1,TMaxHWT_F,FP2,False,False) ' added 29May2009 AMcHugh Maximum (1,RadTankHWT_F,FP2,False,False) ' added 29May2009 AMcHugh Minimum (1,RadTankBTU_BTU_H,FP2,False,False) Minimum (1,RadTankVol_GPH,FP2,False,False) Minimum (1,RadTankST_F,FP2,False,False) Minimum (1,RadTankRT_F,FP2,False,False) Minimum (1,RadTankDT_F,FP2,False,False) Minimum (1,RadTankTBTU_BTU,FP2,False,False) Minimum (1,TMaxHDBTU_BTU_H,FP2,False,False) Minimum (1,TMaxHDVol_GPH,FP2,False,False) Minimum (1,TMaxHDST_F,FP2,False,False) Minimum (1,TMaxHDRT_F,FP2,False,False) Minimum (1,TMaxHDDT_F,FP2,False,False) Minimum (1,TMaxHDTBTU_BTU,FP2,False,False) Minimum (1,TMaxBTU_BTU_H,FP2,False,False) Minimum (1,TMaxVol_GPH,FP2,False,False) Minimum (1,TMaxST_F,FP2,False,False) Minimum (1,TMaxRT_F,FP2,False,False) Minimum (1,TMaxDT_F,FP2,False,False) Minimum (1,TMaxTBTU_BTU,FP2,False,False) Minimum (1,TMaxHWT_F,FP2,False,False) ' added 29May2009 AMcHugh Minimum (1,RadTankHWT_F,FP2,False,False) ' added 29May2009 AMcHugh EndTable DataTable (HourlyEnergyCon,1,-1) DataInterval (0,60,Min,10) Sample (1,BldgLo_kw,FP2) Sample (1,BldgHi_kw,FP2) Sample (1,BldgDemand_kw,FP2) Sample (1,BldgPwrFac,FP2) Sample (1,BldgCurrent_A,FP2) Average (1,BldgLo_kw,FP2,False) Average (1,BldgHi_kw,FP2,False) Average (1,BldgDemand_kw,FP2,False) Average (1,BldgPwrFac,FP2,False) Average (1,BldgCurrent_A,FP2,False) Maximum (1,BldgLo_kw,FP2,False,False) Maximum (1,BldgHi_kw,FP2,False,False) Maximum (1,BldgDemand_kw,FP2,False,False) Maximum (1,BldgPwrFac,FP2,False,False) Maximum (1,BldgCurrent_A,FP2,False,False) Minimum (1,BldgLo_kw,FP2,False,False) Minimum (1,BldgHi_kw,FP2,False,False) Minimum (1,BldgDemand_kw,FP2,False,False) Minimum (1,BldgPwrFac,FP2,False,False) Minimum (1,BldgCurrent_A,FP2,False,False) Sample (1,HourlyUsage_kw,FP2) ' this is the computed Usage EndTable 'Daily table DataTable (DailyRadHeat,True,-1) DataInterval (0,1440,Min,10) Sample (1,Blr1Fuel_G,FP2) Sample (1,BlrSupTemp_F,FP2) Sample (1,BlrRetTemp_F,FP2) Sample (1,Blr1Stack_F,FP2) Sample (1,BLR1BTU_BTU_H,FP2) Sample (1,BLR1Vol_GPM,FP2) Sample (1,BLR1ST_F,FP2) Sample (1,BLR1RT_F,FP2) Sample (1,BLR1DT_F,FP2) Sample (1,BLR1TBTU_BTU,FP2) Average (1,Blr1Fuel_G,FP2,False) Average (1,BlrSupTemp_F,FP2,False) Average (1,BlrRetTemp_F,FP2,False) Average (1,Blr1Stack_F,FP2,False) Average (1,BLR1BTU_BTU_H,FP2,False) Average (1,BLR1Vol_GPM,FP2,False) Average (1,BLR1ST_F,FP2,False) Average (1,BLR1RT_F,FP2,False) Average (1,BLR1DT_F,FP2,False) Average (1,BLR1TBTU_BTU,FP2,False) Maximum (1,Blr1Fuel_G,FP2,False,False) Maximum (1,BlrSupTemp_F,FP2,False,False) Maximum (1,BlrRetTemp_F,FP2,False,False) Maximum (1,Blr1Stack_F,FP2,False,False) Maximum (1,BLR1BTU_BTU_H,FP2,False,False) Maximum (1,BLR1Vol_GPM,FP2,False,False) Maximum (1,BLR1ST_F,FP2,False,False) Maximum (1,BLR1RT_F,FP2,False,False) Maximum (1,BLR1DT_F,FP2,False,False) Maximum (1,BLR1TBTU_BTU,FP2,False,False) Minimum (1,Blr1Fuel_G,FP2,False,False) Minimum (1,BlrSupTemp_F,FP2,False,False) Minimum (1,BlrRetTemp_F,FP2,False,False) Minimum (1,Blr1Stack_F,FP2,False,False) Minimum (1,BLR1BTU_BTU_H,FP2,False,False) Minimum (1,BLR1Vol_GPM,FP2,False,False) Minimum (1,BLR1ST_F,FP2,False,False) Minimum (1,BLR1RT_F,FP2,False,False) Minimum (1,BLR1DT_F,FP2,False,False) Minimum (1,BLR1TBTU_BTU,FP2,False,False) EndTable DataTable (DailyBsmntLabHt,1,-1) DataInterval (0,1440,Min,10) Sample (1,Blr2Fuel_G,FP2) Sample (1,Blr3Fuel_G,FP2) Sample (1,Blr2Stack_F,FP2) Sample (1,Blr3Stack_F,FP2) Sample (1,BLR2BTU_BTU_H,FP2) Sample (1,BLR2Vol_GPM,FP2) Sample (1,BLR2ST_F,FP2) Sample (1,BLR2RT_F,FP2) Sample (1,BLR2DT_F,FP2) Sample (1,BLR2TBTU_BTU,FP2) Sample (1,BLR3BTU_BTU_H,FP2) Sample (1,BLR3Vol_GPM,FP2) Sample (1,BLR3ST_F,FP2) Sample (1,BLR3RT_F,FP2) Sample (1,BLR3DT_F,FP2) Sample (1,BLR3TBTU_BTU,FP2) Average (1,Blr2Fuel_G,FP2,False) Average (1,Blr3Fuel_G,FP2,False) Average (1,Blr2Stack_F,FP2,False) Average (1,Blr3Stack_F,FP2,False) Average (1,BLR2BTU_BTU_H,FP2,False) Average (1,BLR2Vol_GPM,FP2,False) Average (1,BLR2ST_F,FP2,False) Average (1,BLR2RT_F,FP2,False) Average (1,BLR2DT_F,FP2,False) Average (1,BLR2TBTU_BTU,FP2,False) Average (1,BLR3BTU_BTU_H,FP2,False) Average (1,BLR3Vol_GPM,FP2,False) Average (1,BLR3ST_F,FP2,False) Average (1,BLR3RT_F,FP2,False) Average (1,BLR3DT_F,FP2,False) Average (1,BLR3TBTU_BTU,FP2,False) Maximum (1,Blr2Fuel_G,FP2,False,False) Maximum (1,Blr3Fuel_G,FP2,False,False) Maximum (1,Blr2Stack_F,FP2,False,False) Maximum (1,Blr3Stack_F,FP2,False,False) Maximum (1,BLR2BTU_BTU_H,FP2,False,False) Maximum (1,BLR2Vol_GPM,FP2,False,False) Maximum (1,BLR2ST_F,FP2,False,False) Maximum (1,BLR2RT_F,FP2,False,False) Maximum (1,BLR2DT_F,FP2,False,False) Maximum (1,BLR2TBTU_BTU,FP2,False,False) Maximum (1,BLR3BTU_BTU_H,FP2,False,False) Maximum (1,BLR3Vol_GPM,FP2,False,False) Maximum (1,BLR3ST_F,FP2,False,False) Maximum (1,BLR3RT_F,FP2,False,False) Maximum (1,BLR3DT_F,FP2,False,False) Maximum (1,BLR3TBTU_BTU,FP2,False,False) Minimum (1,Blr2Fuel_G,FP2,False,False) Minimum (1,Blr3Fuel_G,FP2,False,False) Minimum (1,Blr2Stack_F,FP2,False,False) Minimum (1,Blr3Stack_F,FP2,False,False) Minimum (1,BLR2BTU_BTU_H,FP2,False,False) Minimum (1,BLR2Vol_GPM,FP2,False,False) Minimum (1,BLR2ST_F,FP2,False,False) Minimum (1,BLR2RT_F,FP2,False,False) Minimum (1,BLR2DT_F,FP2,False,False) Minimum (1,BLR2TBTU_BTU,FP2,False,False) Minimum (1,BLR3BTU_BTU_H,FP2,False,False) Minimum (1,BLR3Vol_GPM,FP2,False,False) Minimum (1,BLR3ST_F,FP2,False,False) Minimum (1,BLR3RT_F,FP2,False,False) Minimum (1,BLR3DT_F,FP2,False,False) Minimum (1,BLR3TBTU_BTU,FP2,False,False) EndTable DataTable (DailyEnv,1,-1) DataInterval (0,1440,Min,10) Sample (1,OAT_F,FP2) Sample (1,OAH_Pct,FP2) Sample (1,HRV1CO2_ppm,FP2) Sample (1,HRV1RMT_F,FP2) Sample (1,HRV1RMH_Pct,FP2) Sample (1,HRV21CO2_ppm,FP2) Sample (1,HRV21RMT_F,FP2) Sample (1,HRV21RMH_pct,FP2) Sample (1,HRV22CO2_ppm,FP2) Sample (1,HRV22RMT_F,FP2) Sample (1,HRV22RMH_pct,FP2) Sample (1,HRV2SAT_F,FP2) Sample (1,HRV3SAT_F,FP2) Sample (1,HRV3CO2_ppm,FP2) Sample (1,HRV42RMT_F,FP2) Sample (1,HRV41RMH_pct,FP2) Sample (1,HRV4SAT_F,FP2) Sample (1,OACO2_ppm,FP2) Sample (1,HRV5CO2_ppm,FP2) Sample (1,HRV5RMT_F,FP2) Sample (1,HRV5RMH_pct,FP2) Sample (1,HRV5SAT_F,FP2) Sample (1,HRV5RAT_F,FP2) Sample (1,HRV5MAD_pct,FP2) Sample (1,Stair05T_F,FP2) Sample (1,Elev07T_F,FP2) Sample (1,Stair111T_F,FP2) Sample (1,Elev112T_F,FP2) Sample (1,SLOffice116T_F,FP2) Sample (1,BackDoor117T_F,FP2) Sample (1,Elev210T_F,FP2) Sample (1,FrontMes211T_F,FP2) Sample (1,Tech213T_F,FP2) Sample (1,RearMes215T_F,FP2) Sample (1,MensRR217F_F,FP2) Average (1,OAT_F,FP2,False) Average (1,OAH_Pct,FP2,False) Average (1,HRV1CO2_ppm,FP2,False) Average (1,HRV1RMT_F,FP2,False) Average (1,HRV1RMH_Pct,FP2,False) Average (1,HRV21CO2_ppm,FP2,False) Average (1,HRV21RMT_F,FP2,False) Average (1,HRV21RMH_pct,FP2,False) Average (1,HRV22CO2_ppm,FP2,False) Average (1,HRV22RMT_F,FP2,False) Average (1,HRV22RMH_pct,FP2,False) Average (1,HRV2SAT_F,FP2,False) Average (1,HRV3SAT_F,FP2,False) Average (1,HRV3CO2_ppm,FP2,False) Average (1,HRV42RMT_F,FP2,False) Average (1,HRV41RMH_pct,FP2,False) Average (1,HRV4SAT_F,FP2,False) Average (1,OACO2_ppm,FP2,False) Average (1,HRV5CO2_ppm,FP2,False) Average (1,HRV5RMT_F,FP2,False) Average (1,HRV5RMH_pct,FP2,False) Average (1,HRV5SAT_F,FP2,False) Average (1,HRV5RAT_F,FP2,False) Average (1,HRV5MAD_pct,FP2,False) Average (1,Stair05T_F,FP2,False) Average (1,Elev07T_F,FP2,False) Average (1,Stair111T_F,FP2,False) Average (1,Elev112T_F,FP2,False) Average (1,SLOffice116T_F,FP2,False) Average (1,BackDoor117T_F,FP2,False) Average (1,Elev210T_F,FP2,False) Average (1,FrontMes211T_F,FP2,False) Average (1,Tech213T_F,FP2,False) Average (1,RearMes215T_F,FP2,False) Average (1,MensRR217F_F,FP2,False) Maximum (1,OAT_F,FP2,False,False) Maximum (1,OAH_Pct,FP2,False,False) Maximum (1,HRV1CO2_ppm,FP2,False,False) Maximum (1,HRV1RMT_F,FP2,False,False) Maximum (1,HRV1RMH_Pct,FP2,False,False) Maximum (1,HRV21CO2_ppm,FP2,False,False) Maximum (1,HRV21RMT_F,FP2,False,False) Maximum (1,HRV21RMH_pct,FP2,False,False) Maximum (1,HRV22CO2_ppm,FP2,False,False) Maximum (1,HRV22RMT_F,FP2,False,False) Maximum (1,HRV22RMH_pct,FP2,False,False) Maximum (1,HRV2SAT_F,FP2,False,False) Maximum (1,HRV3SAT_F,FP2,False,False) Maximum (1,HRV3CO2_ppm,FP2,False,False) Maximum (1,HRV42RMT_F,FP2,False,False) Maximum (1,HRV41RMH_pct,FP2,False,False) Maximum (1,HRV4SAT_F,FP2,False,False) Maximum (1,OACO2_ppm,FP2,False,False) Maximum (1,HRV5CO2_ppm,FP2,False,False) Maximum (1,HRV5RMT_F,FP2,False,False) Maximum (1,HRV5RMH_pct,FP2,False,False) Maximum (1,HRV5SAT_F,FP2,False,False) Maximum (1,HRV5RAT_F,FP2,False,False) Maximum (1,HRV5MAD_pct,FP2,False,False) Maximum (1,Stair05T_F,FP2,False,False) Maximum (1,Elev07T_F,FP2,False,False) Maximum (1,Stair111T_F,FP2,False,False) Maximum (1,Elev112T_F,FP2,False,False) Maximum (1,SLOffice116T_F,FP2,False,False) Maximum (1,BackDoor117T_F,FP2,False,False) Maximum (1,Elev210T_F,FP2,False,False) Maximum (1,FrontMes211T_F,FP2,False,False) Maximum (1,Tech213T_F,FP2,False,False) Maximum (1,RearMes215T_F,FP2,False,False) Maximum (1,MensRR217F_F,FP2,False,False) Minimum (1,OAT_F,FP2,False,False) Minimum (1,OAH_Pct,FP2,False,False) Minimum (1,HRV1CO2_ppm,FP2,False,False) Minimum (1,HRV1RMT_F,FP2,False,False) Minimum (1,HRV1RMH_Pct,FP2,False,False) Minimum (1,HRV21CO2_ppm,FP2,False,False) Minimum (1,HRV21RMT_F,FP2,False,False) Minimum (1,HRV21RMH_pct,FP2,False,False) Minimum (1,HRV22CO2_ppm,FP2,False,False) Minimum (1,HRV22RMT_F,FP2,False,False) Minimum (1,HRV22RMH_pct,FP2,False,False) Minimum (1,HRV2SAT_F,FP2,False,False) Minimum (1,HRV3SAT_F,FP2,False,False) Minimum (1,HRV3CO2_ppm,FP2,False,False) Minimum (1,HRV42RMT_F,FP2,False,False) Minimum (1,HRV41RMH_pct,FP2,False,False) Minimum (1,HRV4SAT_F,FP2,False,False) Minimum (1,OACO2_ppm,FP2,False,False) Minimum (1,HRV5CO2_ppm,FP2,False,False) Minimum (1,HRV5RMT_F,FP2,False,False) Minimum (1,HRV5RMH_pct,FP2,False,False) Minimum (1,HRV5SAT_F,FP2,False,False) Minimum (1,HRV5RAT_F,FP2,False,False) Minimum (1,HRV5MAD_pct,FP2,False,False) Minimum (1,Stair05T_F,FP2,False,False) Minimum (1,Elev07T_F,FP2,False,False) Minimum (1,Stair111T_F,FP2,False,False) Minimum (1,Elev112T_F,FP2,False,False) Minimum (1,SLOffice116T_F,FP2,False,False) Minimum (1,BackDoor117T_F,FP2,False,False) Minimum (1,Elev210T_F,FP2,False,False) Minimum (1,FrontMes211T_F,FP2,False,False) Minimum (1,Tech213T_F,FP2,False,False) Minimum (1,RearMes215T_F,FP2,False,False) Minimum (1,MensRR217F_F,FP2,False,False) EndTable DataTable (DailyPV,1,-1) DataInterval (0,1440,Min,10) Sample (1,PV1VDC_VDC,FP2) Sample (1,PV2VDC_VDC,FP2) Sample (1,PV3VDC_VDC,FP2) Sample (1,PV4VDC_VDC,FP2) Sample (1,PV1Amps_A,FP2) Sample (1,PV2Amps_A,FP2) Sample (1,PV3Amps_A,FP2) Sample (1,PV4Amps_A,FP2) Sample (1,PV1Lo_kw,FP2) Sample (1,PV1Hi_kw,FP2) Sample (1,PV1Demand_kw,FP2) Sample (1,PV1PwrFac,FP2) Sample (1,PV1Current_A,FP2) Sample (1,PV2Lo_kw,FP2) Sample (1,PV2Hi_kw,FP2) Sample (1,PV2Demand_kw,FP2) Sample (1,PV2PwrFac,FP2) Sample (1,PV2Current_A,FP2) Sample (1,PV3Lo_kw,FP2) Sample (1,PV3Hi_kw,FP2) Sample (1,PV3Demand_kw,FP2) Sample (1,PV3PwrFac,FP2) Sample (1,PV3Current_A,FP2) Sample (1,PV4Lo_kw,FP2) Sample (1,PV4Hi_kw,FP2) Sample (1,PV4Demand_kw,FP2) Sample (1,PV4PwrFac,FP2) Sample (1,PV4Current_A,FP2) Average (1,PV1VDC_VDC,FP2,False) Average (1,PV2VDC_VDC,FP2,False) Average (1,PV3VDC_VDC,FP2,False) Average (1,PV4VDC_VDC,FP2,False) Average (1,PV1Amps_A,FP2,False) Average (1,PV2Amps_A,FP2,False) Average (1,PV3Amps_A,FP2,False) Average (1,PV4Amps_A,FP2,False) Average (1,PV1Lo_kw,FP2,False) Average (1,PV1Hi_kw,FP2,False) Average (1,PV1Demand_kw,FP2,False) Average (1,PV1PwrFac,FP2,False) Average (1,PV1Current_A,FP2,False) Average (1,PV2Lo_kw,FP2,False) Average (1,PV2Hi_kw,FP2,False) Average (1,PV2Demand_kw,FP2,False) Average (1,PV2PwrFac,FP2,False) Average (1,PV2Current_A,FP2,False) Average (1,PV3Lo_kw,FP2,False) Average (1,PV3Hi_kw,FP2,False) Average (1,PV3Demand_kw,FP2,False) Average (1,PV3PwrFac,FP2,False) Average (1,PV3Current_A,FP2,False) Average (1,PV4Lo_kw,FP2,False) Average (1,PV4Hi_kw,FP2,False) Average (1,PV4Demand_kw,FP2,False) Average (1,PV4PwrFac,FP2,False) Average (1,PV4Current_A,FP2,False) Maximum (1,PV1VDC_VDC,FP2,False,False) Maximum (1,PV2VDC_VDC,FP2,False,False) Maximum (1,PV3VDC_VDC,FP2,False,False) Maximum (1,PV4VDC_VDC,FP2,False,False) Maximum (1,PV1Amps_A,FP2,False,False) Maximum (1,PV2Amps_A,FP2,False,False) Maximum (1,PV3Amps_A,FP2,False,False) Maximum (1,PV4Amps_A,FP2,False,False) Maximum (1,BldgLo_kw,FP2,False,False) Maximum (1,BldgHi_kw,FP2,False,False) Maximum (1,BldgDemand_kw,FP2,False,False) Maximum (1,BldgPwrFac,FP2,False,False) Maximum (1,BldgCurrent_A,FP2,False,False) Maximum (1,PV1Lo_kw,FP2,False,False) Maximum (1,PV1Hi_kw,FP2,False,False) Maximum (1,PV1Demand_kw,FP2,False,False) Maximum (1,PV1PwrFac,FP2,False,False) Maximum (1,PV1Current_A,FP2,False,False) Maximum (1,PV2Lo_kw,FP2,False,False) Maximum (1,PV2Hi_kw,FP2,False,False) Maximum (1,PV2Demand_kw,FP2,False,False) Maximum (1,PV2PwrFac,FP2,False,False) Maximum (1,PV2Current_A,FP2,False,False) Maximum (1,PV3Lo_kw,FP2,False,False) Maximum (1,PV3Hi_kw,FP2,False,False) Maximum (1,PV3Demand_kw,FP2,False,False) Maximum (1,PV3PwrFac,FP2,False,False) Maximum (1,PV3Current_A,FP2,False,False) Maximum (1,PV4Lo_kw,FP2,False,False) Maximum (1,PV4Hi_kw,FP2,False,False) Maximum (1,PV4Demand_kw,FP2,False,False) Maximum (1,PV4PwrFac,FP2,False,False) Maximum (1,PV4Current_A,FP2,False,False) Minimum (1,PV1VDC_VDC,FP2,False,False) Minimum (1,PV2VDC_VDC,FP2,False,False) Minimum (1,PV3VDC_VDC,FP2,False,False) Minimum (1,PV4VDC_VDC,FP2,False,False) Minimum (1,PV1Amps_A,FP2,False,False) Minimum (1,PV2Amps_A,FP2,False,False) Minimum (1,PV3Amps_A,FP2,False,False) Minimum (1,PV4Amps_A,FP2,False,False) Minimum (1,BldgLo_kw,FP2,False,False) Minimum (1,BldgHi_kw,FP2,False,False) Minimum (1,BldgDemand_kw,FP2,False,False) Minimum (1,BldgPwrFac,FP2,False,False) Minimum (1,BldgCurrent_A,FP2,False,False) Minimum (1,PV1Lo_kw,FP2,False,False) Minimum (1,PV1Hi_kw,FP2,False,False) Minimum (1,PV1Demand_kw,FP2,False,False) Minimum (1,PV1PwrFac,FP2,False,False) Minimum (1,PV1Current_A,FP2,False,False) Minimum (1,PV2Lo_kw,FP2,False,False) Minimum (1,PV2Hi_kw,FP2,False,False) Minimum (1,PV2Demand_kw,FP2,False,False) Minimum (1,PV2PwrFac,FP2,False,False) Minimum (1,PV2Current_A,FP2,False,False) Minimum (1,PV3Lo_kw,FP2,False,False) Minimum (1,PV3Hi_kw,FP2,False,False) Minimum (1,PV3Demand_kw,FP2,False,False) Minimum (1,PV3PwrFac,FP2,False,False) Minimum (1,PV3Current_A,FP2,False,False) Minimum (1,PV4Lo_kw,FP2,False,False) Minimum (1,PV4Hi_kw,FP2,False,False) Minimum (1,PV4Demand_kw,FP2,False,False) Minimum (1,PV4PwrFac,FP2,False,False) Minimum (1,PV4Current_A,FP2,False,False) EndTable DataTable (DailyDomWater,1,-1) DataInterval (0,1440,Min,10) Sample (1,DomTank1Lvl_ft,FP2) Sample (1,DomTank2Lvl_ft,FP2) Average (1,DomTank1Lvl_ft,FP2,False) Average (1,DomTank2Lvl_ft,FP2,False) Maximum (1,DomTank1Lvl_ft,FP2,False,False) Maximum (1,DomTank2Lvl_ft,FP2,False,False) Minimum (1,DomTank1Lvl_ft,FP2,False,False) Minimum (1,DomTank2Lvl_ft,FP2,False,False) EndTable DataTable (DailySolDomHot,1,-1) DataInterval (0,1440,Min,10) Sample (1,DomBTU_BTU_H,FP2) Sample (1,DomVol_GPH,FP2) Sample (1,DomST_F,FP2) Sample (1,DomRT_F,FP2) Sample (1,DomDT_F,FP2) Sample (1,DomTBTU_BTU,FP2) Sample (1,DomTankHWT_F,FP2) ' added 28May2009 AMcHugh Sample (1,HelioBTU_BTU_H,FP2) Sample (1,HelioVol_GPH,FP2) Sample (1,HelioST_F,FP2) Sample (1,HelioRT_F,FP2) Sample (1,HelioDT_F,FP2) Sample (1,HelioTBTU_BTU,FP2) Sample (1,HelioHDBTU_BTU_H,FP2) Sample (1,HelioHDVol_GPH,FP2) Sample (1,HelioHDST_F,FP2) Sample (1,HelioHDRT_F,FP2) Sample (1,HelioHDDT_F,FP2) Sample (1,HelioHDTBTU_BTU,FP2) Average (1,DomBTU_BTU_H,FP2,False) Average (1,DomVol_GPH,FP2,False) Average (1,DomST_F,FP2,False) Average (1,DomRT_F,FP2,False) Average (1,DomDT_F,FP2,False) Average (1,DomTBTU_BTU,FP2,False) Average (1,DomTankHWT_F,FP2,False) ' added 28May2009 AMcHugh Average (1,HelioBTU_BTU_H,FP2,False) Average (1,HelioVol_GPH,FP2,False) Average (1,HelioST_F,FP2,False) Average (1,HelioRT_F,FP2,False) Average (1,HelioDT_F,FP2,False) Average (1,HelioTBTU_BTU,FP2,False) Average (1,HelioHDBTU_BTU_H,FP2,False) Average (1,HelioHDVol_GPH,FP2,False) Average (1,HelioHDST_F,FP2,False) Average (1,HelioHDRT_F,FP2,False) Average (1,HelioHDDT_F,FP2,False) Average (1,HelioHDTBTU_BTU,FP2,False) Maximum (1,DomBTU_BTU_H,FP2,False,False) Maximum (1,DomVol_GPH,FP2,False,False) Maximum (1,DomST_F,FP2,False,False) Maximum (1,DomRT_F,FP2,False,False) Maximum (1,DomDT_F,FP2,False,False) Maximum (1,DomTBTU_BTU,FP2,False,False) Maximum (1,DomTankHWT_F,FP2,False,False) ' added 28May2009 AMcHugh Maximum (1,HelioBTU_BTU_H,FP2,False,False) Maximum (1,HelioVol_GPH,FP2,False,False) Maximum (1,HelioST_F,FP2,False,False) Maximum (1,HelioRT_F,FP2,False,False) Maximum (1,HelioDT_F,FP2,False,False) Maximum (1,HelioTBTU_BTU,FP2,False,False) Maximum (1,HelioHDBTU_BTU_H,FP2,False,False) Maximum (1,HelioHDVol_GPH,FP2,False,False) Maximum (1,HelioHDST_F,FP2,False,False) Maximum (1,HelioHDRT_F,FP2,False,False) Maximum (1,HelioHDDT_F,FP2,False,False) Maximum (1,HelioHDTBTU_BTU,FP2,False,False) Minimum (1,DomBTU_BTU_H,FP2,False,False) Minimum (1,DomVol_GPH,FP2,False,False) Minimum (1,DomST_F,FP2,False,False) Minimum (1,DomRT_F,FP2,False,False) Minimum (1,DomDT_F,FP2,False,False) Minimum (1,DomTBTU_BTU,FP2,False,False) Minimum (1,DomTankHWT_F,FP2,False,False) ' added 28May2009 AMcHugh Minimum (1,HelioBTU_BTU_H,FP2,False,False) Minimum (1,HelioVol_GPH,FP2,False,False) Minimum (1,HelioST_F,FP2,False,False) Minimum (1,HelioRT_F,FP2,False,False) Minimum (1,HelioDT_F,FP2,False,False) Minimum (1,HelioTBTU_BTU,FP2,False,False) Minimum (1,HelioHDBTU_BTU_H,FP2,False,False) Minimum (1,HelioHDVol_GPH,FP2,False,False) Minimum (1,HelioHDST_F,FP2,False,False) Minimum (1,HelioHDRT_F,FP2,False,False) Minimum (1,HelioHDDT_F,FP2,False,False) Minimum (1,HelioHDTBTU_BTU,FP2,False,False) EndTable DataTable (DailySolHydrnc,1,-1) DataInterval (0,1440,Min,10) Sample (1,RadTankBTU_BTU_H,FP2) Sample (1,RadTankVol_GPH,FP2) Sample (1,RadTankST_F,FP2) Sample (1,RadTankRT_F,FP2) Sample (1,RadTankDT_F,FP2) Sample (1,RadTankTBTU_BTU,FP2) Sample (1,TMaxHDBTU_BTU_H,FP2) Sample (1,TMaxHDVol_GPH,FP2) Sample (1,TMaxHDST_F,FP2) Sample (1,TMaxHDRT_F,FP2) Sample (1,TMaxHDDT_F,FP2) Sample (1,TMaxHDTBTU_BTU,FP2) Sample (1,TMaxBTU_BTU_H,FP2) Sample (1,TMaxVol_GPH,FP2) Sample (1,TMaxST_F,FP2) Sample (1,TMaxRT_F,FP2) Sample (1,TMaxDT_F,FP2) Sample (1,TMaxTBTU_BTU,FP2) Sample (1,TMaxHWT_F,FP2) ' added 29May2009 AMcHugh Sample (1,RadTankHWT_F,FP2) ' added 29May2009 AMcHugh Average (1,RadTankBTU_BTU_H,FP2,False) Average (1,RadTankVol_GPH,FP2,False) Average (1,RadTankST_F,FP2,False) Average (1,RadTankRT_F,FP2,False) Average (1,RadTankDT_F,FP2,False Average (1,RadTankTBTU_BTU,FP2,False) Average (1,TMaxHDBTU_BTU_H,FP2,False) Average (1,TMaxHDVol_GPH,FP2,False) Average (1,TMaxHDST_F,FP2,False) Average (1,TMaxHDRT_F,FP2,False) Average (1,TMaxHDDT_F,FP2,False) Average (1,TMaxHDTBTU_BTU,FP2,False) Average (1,TMaxBTU_BTU_H,FP2,False) Average (1,TMaxVol_GPH,FP2,False) Average (1,TMaxST_F,FP2,False) Average (1,TMaxRT_F,FP2,False) Average (1,TMaxDT_F,FP2,False) Average (1,TMaxTBTU_BTU,FP2,False) Average (1,TMaxHWT_F,FP2,False) ' added 29May2009 AMcHugh Average (1,RadTankHWT_F,FP2,False) ' added 29May2009 AMcHugh Maximum (1,RadTankBTU_BTU_H,FP2,False,False) Maximum (1,RadTankVol_GPH,FP2,False,False) Maximum (1,RadTankST_F,FP2,False,False) Maximum (1,RadTankRT_F,FP2,False,False) Maximum (1,RadTankDT_F,FP2,False,False) Maximum (1,RadTankTBTU_BTU,FP2,False,False) Maximum (1,TMaxHDBTU_BTU_H,FP2,False,False) Maximum (1,TMaxHDVol_GPH,FP2,False,False) Maximum (1,TMaxHDST_F,FP2,False,False) Maximum (1,TMaxHDRT_F,FP2,False,False) Maximum (1,TMaxHDDT_F,FP2,False,False) Maximum (1,TMaxHDTBTU_BTU,FP2,False,False) Maximum (1,TMaxBTU_BTU_H,FP2,False,False) Maximum (1,TMaxVol_GPH,FP2,False,False) Maximum (1,TMaxST_F,FP2,False,False) Maximum (1,TMaxRT_F,FP2,False,False) Maximum (1,TMaxDT_F,FP2,False,False) Maximum (1,TMaxTBTU_BTU,FP2,False,False) Maximum (1,TMaxHWT_F,FP2,False,False) ' added 29May2009 AMcHugh Maximum (1,RadTankHWT_F,FP2,False,False) ' added 29May2009 AMcHugh Minimum (1,RadTankBTU_BTU_H,FP2,False,False) Minimum (1,RadTankVol_GPH,FP2,False,False) Minimum (1,RadTankST_F,FP2,False,False) Minimum (1,RadTankRT_F,FP2,False,False) Minimum (1,RadTankDT_F,FP2,False,False) Minimum (1,RadTankTBTU_BTU,FP2,False,False) Minimum (1,TMaxHDBTU_BTU_H,FP2,False,False) Minimum (1,TMaxHDVol_GPH,FP2,False,False) Minimum (1,TMaxHDST_F,FP2,False,False) Minimum (1,TMaxHDRT_F,FP2,False,False) Minimum (1,TMaxHDDT_F,FP2,False,False) Minimum (1,TMaxHDTBTU_BTU,FP2,False,False) Minimum (1,TMaxBTU_BTU_H,FP2,False,False) Minimum (1,TMaxVol_GPH,FP2,False,False) Minimum (1,TMaxST_F,FP2,False,False) Minimum (1,TMaxRT_F,FP2,False,False) Minimum (1,TMaxDT_F,FP2,False,False) Minimum (1,TMaxTBTU_BTU,FP2,False,False) Minimum (1,TMaxHWT_F,FP2,False,False) ' added 29May2009 AMcHugh Minimum (1,RadTankHWT_F,FP2,False,False) ' added 29May2009 AMcHugh EndTable DataTable (DailyEnergyCon,1,-1) DataInterval (0,1440,Min,10) Sample (1,BldgLo_kw,FP2) Sample (1,BldgHi_kw,FP2) Sample (1,BldgDemand_kw,FP2) Sample (1,BldgPwrFac,FP2) Sample (1,BldgCurrent_A,FP2) Average (1,BldgLo_kw,FP2,False) Average (1,BldgHi_kw,FP2,False) Average (1,BldgDemand_kw,FP2,False) Average (1,BldgPwrFac,FP2,False) Average (1,BldgCurrent_A,FP2,False) Maximum (1,BldgLo_kw,FP2,False,False) Maximum (1,BldgHi_kw,FP2,False,False) Maximum (1,BldgDemand_kw,FP2,False,False) Maximum (1,BldgPwrFac,FP2,False,False) Maximum (1,BldgCurrent_A,FP2,False,False) Minimum (1,BldgLo_kw,FP2,False,False) Minimum (1,BldgHi_kw,FP2,False,False) Minimum (1,BldgDemand_kw,FP2,False,False) Minimum (1,BldgPwrFac,FP2,False,False) Minimum (1,BldgCurrent_A,FP2,False,False) Sample (1,DailyUsage_kw,FP2) ' this is the computed Usage EndTable 'Define Subroutines 'Sub 'EnterSub instructions here 'EndSub 'Main Program BeginProg SerialOpen (Com2,19200,3,100,1000) Scan (5,Sec,0,0) PanelTemp (LoggerTemp_C,250) Battery (BattVolts_V) '1-100 ModBusMaster (Result,Com2,19200,1,3,ModBusVariable,1,100,3,100) '101-146 ModBusMaster (Result,Com2,19200,1,3,ModBusVariable2,101,46,3,100) For i = 1 To 100 ModbusVarFloat(i) = ModbusVariable(i) Next i For i = 1 To 46 ModbusVar2Float(i) = ModbusVariable2(i) Next i ' divide appropriate modbus variable by 100 For i = 4 To 10 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 13 To 20 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 22 To 25 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 27 To 28 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 30 To 33 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 35 To 40 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i ModbusVarFloat(43) = ModbusVariable(43)/100 For i = 45 To 46 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 48 To 49 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 52 To 72 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 74 To 78 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 80 To 84 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 86 To 90 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 92 To 96 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i For i = 98 To 100 ModbusVarFloat(i) = ModbusVariable(i)/100 Next i ' Second set starts here. For i = 1 To 2 ModbusVar2Float(i) = ModbusVariable2(i)/100 Next i For i = 4 To 8 ModbusVar2Float(i) = ModbusVariable2(i)/100 Next i For i = 10 To 14 ModbusVar2Float(i) = ModbusVariable2(i)/100 Next i For i = 16 To 20 ModbusVar2Float(i) = ModbusVariable2(i)/100 Next i ModbusVar2Float(23) = ModbusVariable2(23)*100 ' yes this is times by 100 For i = 24 To 26 ModbusVar2Float(i) = ModbusVariable2(i)/100 Next i For i = 29 To 31 ModbusVar2Float(i) = ModbusVariable2(i)/100 Next i For i = 34 To 36 ModbusVar2Float(i) = ModbusVariable2(i)/100 Next i For i = 39 To 41 ModbusVar2Float(i) = ModbusVariable2(i)/100 Next i For i = 44 To 46 ModbusVar2Float(i) = ModbusVariable2(i)/100 Next i ' create Usage values. ' it is assumed the usage counter counts from 0 to 2050 kw then resets to 0. ' it is assumed that there will not be more than one counter reset transistion in a day (hour, or 1/4 hour). ' it is assumed there will never be a change from 1500 (through 2050) to 500, or 1000 kw usage, ' in a day (15 min or hourly period). If IfTime (0,15,Min) Then ' if we crossed a counter reset, add the extra part above 2050 to the last part for the complete usage ' if the BldgLo value 15 miutes ago was big and this one is small, we need to add the piece up to 2050 on. If (LastQHBldgLo > 1500 AND LastQHBldgLo < 2051) AND (BldgLo_kw < 500) Then QuarterHrUsage_kw = (BldgLo_kw + (2050 - LastQHBldgLo)) Else ' if we don't reset the counter, usage is simply the difference between current and last. QuarterHrUsage_kw = BldgLo_kw - LastQHBldgLo EndIf ' set last = to current LastQHBldgLo = BldgLo_kw EndIf 'Hourly Usage If IfTime (0,60,Min) Then ' if we crossed a counter reset, add the extra part above 2050 to the last part for the complete usage ' if the BldgLo value 15 miutes ago was big and this one is small, we need to add the piece up to 2050 on. If (LastHourlyBldgLo > 1500 AND LastHourlyBldgLo < 2051) AND (BldgLo_kw < 500) Then HourlyUsage_kw = (BldgLo_kw + (2050 - LastHourlyBldgLo)) Else ' if we don't reset the counter, usage is simply the difference between current and last. HourlyUsage_kw = BldgLo_kw - LastHourlyBldgLo EndIf ' set last = to current LastHourlyBldgLo = BldgLo_kw EndIf 'Daily Usage If IfTime (0,1440,Min) Then ' if we crossed a counter reset, add the extra part above 2050 to the last part for the complete usage ' if the BldgLo value 15 miutes ago was big and this one is small, we need to add the piece up to 2050 on. If (LastDailyBldgLo > 1500 AND LastDailyBldgLo < 2051) AND (BldgLo_kw < 500) Then DailyUsage_kw = (BldgLo_kw + (2050 - LastDailyBldgLo)) Else ' if we don't reset the counter, usage is simply the difference between current and last. DailyUsage_kw = BldgLo_kw - LastDailyBldgLo EndIf ' set last = to current LastDailyBldgLo = BldgLo_kw EndIf 'Call Output Tables CallTable (HourlyDiag) CallTable FifteenMinPV CallTable FifteenMinRadHeat CallTable FifteenMinBsmntLabHt CallTable FifteenMinEnv CallTable FifteenMinDomWater CallTable FifteenMinSolDomHot CallTable FifteenMinSolHydrnc CallTable FifteenMinEnergyCon CallTable HourlyPV CallTable HourlyRadHeat CallTable HourlyBsmntLabHt CallTable HourlyEnv CallTable HourlyDomWater CallTable HourlySolDomHot CallTable HourlySolHydrnc CallTable HourlyEnergyCon CallTable DailyPV CallTable DailyRadHeat CallTable DailyBsmntLabHt CallTable DailyEnv CallTable DailyDomWater CallTable DailySolDomHot CallTable DailySolHydrnc CallTable DailyEnergyCon NextScan EndProg